System Installation and Configuration | en
13
Bosch Security Systems, Inc.
System Reference Guide
F01U087835 | 02 | 2008.10
2.2
Install System Components
2.2.1
Install the wLSN Hub
1.
Separate the wLSN Hub from its base.
2.
Set the wLSN Hub's rotary switches to enable RFSS mode: S1 = 9, S2 = 2, S3 = 0.
This is the setting required for the RFSS site test. Refer to
Figure 1.1
, Page 6.
3.
Connect the wLSN Hub's data bus to the control panel's data bus. The wLSN Hub's
terminal block is removable.
–
Wire Gauge:
0.14 mm to 1.5 mm (18 AWG to 24 AWG)
–
Wire Length (sLSN Hub to control panel):
<= 100 m
4.
Reconnect the wLSN Hub and base, and then lock the wLSN Hub.
5.
Mount the wLSN Hub temporarily in the desired location. You might need to relocate the
wLSN Hub if it does not pass RFSS testing.
2.2.2
Install the Control Panel Enclosure
1.
Remove the desired knockouts from the control panel enclosure and optional mounting
skirt.
2.
Attach the optional mounting skirt to the enclosure.
3.
Route the wires through the desired knockouts.
4.
Mount the enclosure to the desired surface. Use proper anchor and screw sets when you
install the enclosure on non-load-bearing surfaces, such as drywall.
i
NOTICE!
–
Use proper anchor and screw sets when installing the enclosure on non-load-bearing
surfaces, such as drywall.
–
Follow anti-static procedures when handling the control panel board. Touch the earth
ground terminal on the control panel board to discharge any static charge before working
on the control panel board.
–
If you install more than one control center, mount them at least 1.2 m apart.
–
Do not install the wLSN Hub within 15 cm (6 in) of the control centers metal enclosure.
i
NOTICE!
Refer to
Figure 1.2
, Page 8 or
Figure 1.3
, Page 8 throughout this section for the location to
install each of the hardware components in the enclosure.