Commissioning
5
HPC 410 – 6721832682 (2021/02)
always be checked here and, if necessary, adjusted and finally
confirmed.
If the system analysis is skipped, the
Commissioning
menu is opened
directly. The sub-menus and settings listed here must be carefully
adjusted according to the installed system. Finally, the settings must be
confirmed.
Table 1 Commissioning with the configuration wizard
Menu item
Control range: Function description
Country information
Set the country and confirm.
Buffer cyl.
Select [Yes] if a buffer cylinder is installed.
Otherwise select [No] and confirm.
Start configuration wizard
[Yes] | [No]: Please ensure before starting the
configuration wizard:
• that all connected modules are installed and
addressed.
• that an outdoor temperature sensor is installed.
Min. outside
temp.
Set the design temperature for the system, DUT
(Dimensioning outdoor temperature). This is the
lowest average outdoor temperature for the region.
The setting affects the slope of the heating curve as it
is the point where the heat source reaches the
highest flow temperature.
VC0 valve
connected
Set this if a 3-way valve is installed between the
buffer cylinder and the heat pump/indoor unit.
Select add. heat
appliance
[Not installed]
[Electric booster heater in series]: this selection
applies to the integrated electrical heater.
[Additional heater with mixer only]: this selection
applies to a mixed additional heater that only runs
when the heat pump is off.
[Add. heater with mixer in parallel]: this selection
applies to a mixed additional heater that is allowed to
run in parallel with the heat pump.
[Hybrid]: this selection applies to an additional
heater that is allowed to run instead of the heat pump
based on the energy price settings.
Mixed aux. heat.
conn
[230V] The mixed additional heater is controlled by
on/off signal.
[0-10V] The mixed additional heater is controlled
based on power demand.
Heating circuit 1
installed
[On the heat appliance]: heating circuit 1 is
connected directly to the heat pump/indoor unit.
[On module]: heating circuit 1 is electrically
connected to a mixing module. Buffer cylinder is
required.
Config. HC1 at
HP
[No HC1 on heat appliance]: no heating circuit
connected to the heat source.
[No own heating circuit pump]: heating circuit 1 is
directly connected to the heat pump/indoor unit
without heating circuit pump.
[Via pump PC1]: heating circuit 1 is directly
connected to the heat pump/indoor unit and
equipped with a heating circuit pump.
Priority heating
circuit 1
Select [Yes] if heating circuit 1 limits the heating
supply to additional heating circuits. Otherwise
select [No] and confirm.
Mixer heating
circuit 1
[Yes] | [No]: setting that defines whether heating
circuit 1 is a heating circuit with mixer.
Mixer runtime
heat circ. 1
0 ... 600 s: setting that specifies the time required
by the mixing valve in heating circuit 1 to turn from
one stop to the other.
Heating system
heat circ. 1
[Radiators] | [Convector] | [Floor]: setting for the
type of heating distribution in the selected heating
circuit.
Ctrl type h. circ.
1
[Outside temp.-compensated]: Weather-
compensated flow temperature controlled by the
outside temperature sensor.
[Outside temp. with base point]: weather-
compensated control, taking a base point into
account.
Rem. ctr. heat.
circuit 1
[None] | [CR10] | [CR10H]: selection of the
corresponding remote room controller for the
heating circuit.
[Heating circuit 2 ... 4]: see [Heating circuit 1 installed], but only the
first heating circuit can be directly connected to the heat source. All
additional heating circuits must be mixed.
DHW install.
[No]: no DHW system installed.
[Heat p.]: a DHW system is activated and connected
directly to the heat pump, either by the integrated
cylinder or externally by a 3-way valve.
[Freshwa.]: a freshwater station is connected.
DHW circ.pump
installed
[No] | [Yes]: setting that specifies whether a DHW
circulation pump is installed in the DHW system and
controlled by the user interface. This menu is not
shown if a freshwater station is installed.
Size of
freshwater
station
[15/20 l/min] | [27 l/min] | [40 l/min]: setting that
specifies the size of the freshwater station.
Freshwater
station
2...Freshwater
station 4
[No]: no further freshwater station is connected.
[MS100]: a freshwater extension station is
connected.
Change
freshwater
configuration
Setting that specifies the configuration of the
freshwater installation. Check and confirm that it
corresponds with the system installed.
Ventilation
installed
[No] | [Yes]: setting that specifies whether or not a
ventilation system is installed and controlled by the
user interface.
Sol.therm.sys.
instlld
[No] | [Yes]: setting that specifies whether or not a
solar thermal system is installed and controlled by
the user interface.
Solar extension
module
[No] | [SM100]: setting that specifies whether or not
a solar extension module is installed and controlled
by the user interface.
Pool mixing
valve
0 ... 600 s: if a mixing valve for a pool is installed and
controlled by the user interface, set the time
required by the valve to turn from one stop to the
other.
Electr. anode in
cylinder
[No] | [Yes]: setting that specifies whether or not an
electric anode is installed in the DHW cylinder.
Fuse size
[16A] | [20A] | [25A] | [32A]: set the main fuse of
the house dedicated to the heating appliance.
Confirming configuration
[Confirm: if all settings correspond to the installed
system.
[Back]: if changes are needed.
Menu item
Control range: Function description