Commissioning

5

HPC 410 – 6721832682 (2021/02)

always be checked here and, if necessary, adjusted and finally 
confirmed.

If the system analysis is skipped, the 

Commissioning

 menu is opened 

directly. The sub-menus and settings listed here must be carefully 
adjusted according to the installed system. Finally, the settings must be 
confirmed.

Table 1 Commissioning with the configuration wizard

Menu item

Control range: Function description

Country information

Set the country and confirm.

Buffer cyl.

Select [Yes] if a buffer cylinder is installed. 
Otherwise select [No] and confirm.

Start configuration wizard

[Yes]  | [No]: Please ensure before starting the 
configuration wizard:

• that all connected modules are installed and 

addressed.

• that an outdoor temperature sensor is installed.

Min. outside 
temp.

Set the design temperature for the system, DUT 
(Dimensioning outdoor temperature). This is the 
lowest average outdoor temperature for the region. 
The setting affects the slope of the heating curve as it 
is the point where the heat source reaches the 
highest flow temperature.

VC0 valve 
connected

Set this if a 3-way valve is installed between the 
buffer cylinder and the heat pump/indoor unit.

Select add. heat 
appliance

[Not installed]

[Electric booster heater in series]: this selection 
applies to the integrated electrical heater.

[Additional heater with mixer only]: this selection 
applies to a mixed additional heater that only runs 
when the heat pump is off.

[Add. heater with mixer in parallel]: this selection 
applies to a mixed additional heater that is allowed to 
run in parallel with the heat pump.

[Hybrid]: this selection applies to an additional 
heater that is allowed to run instead of the heat pump 
based on the energy price settings.

Mixed aux. heat. 
conn

[230V] The mixed additional heater is controlled by 
on/off signal.
[0-10V] The mixed additional heater is controlled 
based on power demand.

Heating circuit 1 
installed

[On the heat appliance]: heating circuit 1 is 
connected directly to the heat pump/indoor unit.

[On module]: heating circuit 1 is electrically 
connected to a mixing module. Buffer cylinder is 
required.

Config. HC1 at 
HP

[No HC1 on heat appliance]: no heating circuit 
connected to the heat source.

[No own heating circuit pump]: heating circuit 1 is 
directly connected to the heat pump/indoor unit 
without heating circuit pump.

[Via pump PC1]: heating circuit 1 is directly 
connected to the heat pump/indoor unit and 
equipped with a heating circuit pump.

Priority heating 
circuit 1

Select [Yes] if heating circuit 1 limits the heating 
supply to additional heating circuits. Otherwise 
select [No] and confirm.

Mixer heating 
circuit 1

[Yes]  | [No]: setting that defines whether heating 
circuit 1 is a heating circuit with mixer.

Mixer runtime 
heat circ. 1

0 ... 600 s: setting that specifies the time required 
by the mixing valve in heating circuit 1 to turn from 
one stop to the other.

Heating system 
heat circ. 1

[Radiators] | [Convector] | [Floor]: setting for the 
type of heating distribution in the selected heating 
circuit.

Ctrl type h. circ. 
1

[Outside temp.-compensated]: Weather-
compensated flow temperature controlled by the 
outside temperature sensor.

[Outside temp. with base point]: weather-
compensated control, taking a base point into 
account.

Rem. ctr. heat. 
circuit 1

[None] | [CR10] | [CR10H]: selection of the 
corresponding remote room controller for the 
heating circuit.

[Heating circuit 2 ... 4]: see [Heating circuit 1 installed], but only the 
first heating circuit can be directly connected to the heat source. All 
additional heating circuits must be mixed.

DHW install.

[No]: no DHW system installed.

[Heat p.]: a DHW system is activated and connected 
directly to the heat pump, either by the integrated 
cylinder or externally by a 3-way valve.

[Freshwa.]: a freshwater station is connected.

DHW circ.pump 
installed

[No] | [Yes]: setting that specifies whether a DHW 
circulation pump is installed in the DHW system and 
controlled by the user interface. This menu is not 
shown if a freshwater station is installed.

Size of 
freshwater 
station

[15/20 l/min] | [27 l/min]  | [40 l/min]: setting that 
specifies the size of the freshwater station.

Freshwater 
station 
2...Freshwater 
station 4

[No]: no further freshwater station is connected.
[MS100]: a freshwater extension station is 
connected.

Change 
freshwater 
configuration

Setting that specifies the configuration of the 
freshwater installation. Check and confirm that it 
corresponds with the system installed.

Ventilation 
installed

[No] | [Yes]: setting that specifies whether or not a 
ventilation system is installed and controlled by the 
user interface.

Sol.therm.sys. 
instlld

[No] | [Yes]: setting that specifies whether or not a 
solar thermal system is installed and controlled by 
the user interface.

Solar extension 
module

[No] | [SM100]: setting that specifies whether or not 
a solar extension module is installed and controlled 
by the user interface.

Pool mixing 
valve

0 ... 600 s: if a mixing valve for a pool is installed and 
controlled by the user interface, set the time 
required by the valve to turn from one stop to the 
other.

Electr. anode in 
cylinder

[No] | [Yes]: setting that specifies whether or not an 
electric anode is installed in the DHW cylinder.

Fuse size

[16A] | [20A] | [25A] | [32A]: set the main fuse of 
the house dedicated to the heating appliance.

Confirming configuration

[Confirm: if all settings correspond to the installed 
system.
[Back]: if changes are needed.

Menu item

Control range: Function description

Содержание HPC 410

Страница 1: ...6721832682 2021 02 Installation instructions for contractors User interface HPC 410 EMS 2 0010031776 002 ...

Страница 2: ...s for the heat pump 6 4 1 1 Menu Heat pump 6 4 1 2 Menu Pumps 7 4 1 3 Menu External connections 7 4 1 4 Menu Smart grid 8 4 1 5 Menu PV system 8 4 2 Additional heater settings 8 4 2 1 Menu Set additional heater 8 4 2 2 Menu Electric auxiliary heater 8 4 2 3 Menu Auxiliary heater with mixer 9 4 3 Heating settings 9 4 3 1 System data 9 4 3 2 Menu Priority heating circuit 1 10 4 3 3 Menu heating circ...

Страница 3: ...CE NOTICE indicates that material damage may occur Important information Theinfosymbolindicatesimportantinformationwherethereisnoriskto people or property 1 2 General safety instructions H Notice for the target group These installation instructions are intended for plumbers heating engineers and electricians All instructions must be observed Failure to comply with instructions may result in materi...

Страница 4: ...2 control system User interface CR102 as a simple remote room controller User interface CR10H as a simple remote room controller with option to measure relative humidity heating cooling circuits MM 100 module for one heating cooling circuit with mixing valve MP 1002 module for a swimming pool MS 1002 module for solar DHW heating MS 2002 module for advanced solar systems Combination is not possible...

Страница 5: ...d confirm Mixer heating circuit 1 Yes No setting that defines whether heating circuit 1 is a heating circuit with mixer Mixer runtime heat circ 1 0 600 s setting that specifies the time required by the mixing valve in heating circuit 1 to turn from one stop to the other Heating system heat circ 1 Radiators Convector Floor setting for the type of heating distribution in the selected heating circuit...

Страница 6: ... system Press and hold the selector until a pop up menu is displayed Select Yes in the menu Switch from standby mode to normal operation To permanently shutdown Disconnectpower from the entire system and all BUS nodes After a prolonged power failure or extended period of idleness the date and time may need to be reset All other settings are retained permanently 3 8 Quick start of heat pump Open th...

Страница 7: ...rt time for the low noise operation Low noise operation until set the stop time for the low noise operation Min outside temp Below this outdoor temperature the heat pump switches over to normal operation Menu item Control range Function description Prim heating pump mode Automatic The primary circulation pump is in operation when any heat source is active When all heat sources are off the circulat...

Страница 8: ... increased DHW peak The energy available in the PV system is used for DHW Yes No If enabled the DHW is heated to the temperature set for DHWoperatingmode DHWcomfort Noheatingisdoneif the holiday program is active Cooling setback mode If Onlycoolwith PV is setto Yes sethowmany degrees the heat pump is allowed to lower the indoor temperature Only cool with PV Cooling mode is activated only if energy...

Страница 9: ... heater is allowed to start and the heat pump is blocked below the set outdoor temperature Alternating operation Bival pt switch mode2 Add heater DHW cylinder Yes No Choose if the DHW cylinder has an electric additional heater installed Menu item Control range Function description Is a buffer cylinder installed Yes No Set if a buffer cylinder is installed in the heating system Config HC1 at HP No ...

Страница 10: ...automatically changes from the setback mode to the heating mode Heat constantly below a certain outside temperature Frost prot Notice to ensure frost protection for the entire heating system set outside temperature dependent frost protection This setting is independent of the set control type Outdoor temp Room Room and outside temp frost protection is deactivated activated on the basis of the temp...

Страница 11: ...etectionisdeactivatedfortheselected heating circuit Menu item Adjustment range Design temperature or End point 30 75 85 C radiator convector 30 45 85 C underfloor heating system The design temperature is only available with weather compensated control without base point The design temperature is the flow temperature that is reached at the minimum outside temperature and therefore affects the steep...

Страница 12: ... protection outside temperature threshold is set It is only effective if Frost prot Outdoor temp or Room and outside temp is set in the menu NOTICE Domestichotwatercarryingpartsmaybedamagedbeyondrepairif thefrostprotectionlimittemperatureissettoolowandinprolonged periods with outside temperature below 0 C Only contractors are permitted to adjust the factory setting of the frost protection limit te...

Страница 13: ...ase Fig 6 2 Holding phase period 1 7 99 days time delay between the beginning of the holding phase duration of the maximum temperature for screed drying and the next phase Fig 6 4 Holding phase temp 20 55 C flow temperature during the holding phase maximum temperature Fig 6 4 Cool down phase incr No cool down phase no cooling phase takes place 1 10 days setting for the time delay between the steps...

Страница 14: ...ed by the heat source Circulation oper mode Off circulation off On circulation permanently on by taking the start frequency into account As DHW system Activate the same time program for circulation as for DHW heating Further information and settingsofthecustomisedtimeprogram userinterface operating instructions Own time program activate customised time program for circulation Further information a...

Страница 15: ...r 3 minutes as soon as there is a short tap 2 10 seconds The pump is then blocked for 10 minutes Automat therm disinfect Yes the thermal disinfection is started automatically at the set time No the thermal disinfection is not started automatically Therm disinfection day Monday Tuesday Sunday weekday on which thermal disinfection is performed Daily heat up thermal disinfection is performed daily Th...

Страница 16: ...in the system can be called up in this menu 4 9 6 Maintenance menu The contact address for a service company can be set in this menu The contactaddress is automatically displayed to the end user in case of a fault Entering company name and telephone number The current cursor position will flash marked by Turn the selector to move the cursor Press the selector to activate the input field Turn and p...

Страница 17: ...rvice providers and or Bosch affiliated enterprises In some cases but only if appropriate data protection is ensured personal data might be transferred to recipients located outside of the European Economic Area Further information are provided on request You can contact our Data Protection Officer under Data Protection Officer Information Security and Privacy C ISP Robert Bosch GmbH Postfach 30 0...

Страница 18: ...ture sensor in the controller in accordance with table If the sensor values matched but the voltage values do not match replace the control unit A01 811 and A41 4051 4052 DHW provision thermal disinfection unsuccessful Test procedure Cause Action A11 1038 Invalid time date Test procedure Cause Action Date time not yet set Set date time Prolonged loss of power supply Avoid voltage failures A11 3061...

Страница 19: ...ion Check parameter settings at the installation level Register room temperature dependent controller for heating circuit 1 4 as remote control Hxx Test procedure Cause Action For instance service interval of heat source elapsed Service required see documents for the heat source A01 5378 Outdoor unit defrost failure Test procedure Cause Action Too low temperature of heating system Open more thermo...

Страница 20: ...ogic ext connection 1 Block compr operation Block HW operation Block heating mode Block cooling mode Overheat protection HC1 ESC blocking time1 on ESC blocking time2 on ESC blocking time3 on Block additional heater PV system External connection 2 External connection 3 External connection 4 Fuse size Manual defrosting Smart grid Heating Selectable peak Forced peak DHW Selectable peak PV system Heat...

Страница 21: ... dry System Screed drying system Screed dry HC 1 4 Screed drying heating circuit 1 4 Start Interrupt Continue DHW settings DHW operation energy manager Switch on temp EM Switch off temperature EM DHW comfort Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay...

Страница 22: ...ion Start Time Save all settings Commissioning complete Diagnosis Function check Activating function checks Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Monit values Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Output limiter Fault displays System information Maintenance Reset Calibration SnapShot ...

Страница 23: ......

Страница 24: ... Cotswold Way Warndon Worcester WR4 9SW United Kingdom Tel 0330 123 9559 worcester bosch co uk 0330 123 3366 TECHNICAL SUPPORT RENEWABLE SUPPORT 0330 123 9229 CONTROLS AND CONNECTIVITY TEAM 0330 123 3641 0330 123 9339 0330 123 9779 0330 123 9119 0330 123 0166 0330 123 9669 ...

Отзывы: