Service menu

 

HPC 410 – 6721832682 (2021/02)

12

Fig. 4

Setting of the heating curve for radiators
Gradient via design temperature T

0

 and minimum outside 

temperature T

1min

Fig. 5

Setting the heating curve for radiators
Parallel shift above Room temperature offset or required room 
temperature

T

1

Outdoor Temperature

T

0

Flow temperature

[1]

Setting: T

0

 = 75 °C, T

1,min

= –10 °C (base curve), limit at T

0,max

 = 

75 °C

[2]

Setting: T

0

 = 80 °C, T

1,min

= –10 °C, limit at T

0,max

 = 80 °C

[3]

Setting: T

0

 = 70 °C, T

1,min

= –20 °C

[4]

Parallel displacement of the base curve [1] by changing the offset 
by +3 or by increasing the desired room temperature, limit at 
T

0,max

 = 80 °C

[5]

Parallel displacement of the base curve [1] by changing the 
offset  -3 or by reducing the desired room temperature, limit at 
T

0,max

 = 75 °C

Simple heating curve

The simple heating curve (

Ctrl type h. circ. 1

Outside temp. with base 

point

) is represented by a straight line. This straight line is described by 

two points: the base point (starting point of the heating curve) and the 
end point.

Table 15 Basic settings of the simple heating curve

Heat constantly below a certain outside temperature

To prevent the system from cooling down, DIN-EN 12831 requires that, 
for the maintaining of a comfortable heat, all heating surfaces and heat 
sources are designed to a defined output. If the adjusted outside 
temperature set under 

Constant heat below

 is undercut, the active 

setback mode is interrupted by normal heating mode.

For example, if the settings 

Setback

Heating off

 : 5 °C and 

Constant 

heat below

: -15 °C are active, the setback mode is activated when the 

adjusted outside temperature is between 5 °C and -15 °C and the heating 
mode is activated below -15 °C. This allows smaller heat emitters to be 
utilised.

Frost protection limit temperature (outside temperature threshold)

Under this menu item the limit temperature for the frost protection 
(outside temperature threshold) is set. It is only effective if 

Frost prot.

Outdoor temp

 or 

Room and outside temp.

 is set in the menu.

NOTICE

Domestic hot water carrying parts may be damaged beyond repair if 
the frost protection limit temperature is set too low and in prolonged 
periods with outside temperature below 0 °C.

▶ Only contractors are permitted to adjust the factory setting of the 

frost protection limit temperature (5 °C).

▶ Do not set the frost protection limit temperature too low. Damage 

caused by a low frost protection limit temperature is not covered by 
the warranty.

▶ Set frost protection limit temperature and frost protection for all 

heating circuits.

▶ To ensure frost protection for the entire heating system, set either 

Outdoor temp

 or 

Room and outside temp.

 in the 

Frost prot.

 menu.

The setting 

Room temperature

 does not offer absolute frost protection, 

because pipework installed in façades, for instance, can freeze. If an 
outside temperature sensor is installed on the other hand, frost 
protection can be assured for the entire heating system regardless of the 
control type set.

4.3.4

Screed drying menu

This menu is only available if at least one under floor heating circuit is 
installed in the system and adjusted.

A screed drying program is set for the selected heating circuit or the 
entire heating system in this menu. To dry a new screed the heating 
system automatically runs the screed drying program once.

In case of a voltage failure the user interface automatically continues 
with the screed drying program. The voltage failure, however, must not 
last longer than the power reserve of the user interface or the maximum 
interruption duration.

 Underfloor heating 

system

Radiator

Minimum outside temperature 
T

1,min

– 10 °C

– 10 °C

Base  point

25 °C

25 °C

0

+10

+20

-10

-20

20

30

40

50

60

70

80

90

C

C

0010021109-001

T

1

T

0

1

2

3

0

+10

+20

-10

-20

20

30

40

50

60

70

80

90

C

0010021110-001

C

T

1

T

0

1

4

5

End point

45 °C

60 °C

Maximum flow temperature 
T

0,max

48 °C

75 °C

Room temperature offset

0.0 K

0.0 K

 Underfloor heating 

system

Radiator

Содержание HPC 410

Страница 1: ...6721832682 2021 02 Installation instructions for contractors User interface HPC 410 EMS 2 0010031776 002 ...

Страница 2: ...s for the heat pump 6 4 1 1 Menu Heat pump 6 4 1 2 Menu Pumps 7 4 1 3 Menu External connections 7 4 1 4 Menu Smart grid 8 4 1 5 Menu PV system 8 4 2 Additional heater settings 8 4 2 1 Menu Set additional heater 8 4 2 2 Menu Electric auxiliary heater 8 4 2 3 Menu Auxiliary heater with mixer 9 4 3 Heating settings 9 4 3 1 System data 9 4 3 2 Menu Priority heating circuit 1 10 4 3 3 Menu heating circ...

Страница 3: ...CE NOTICE indicates that material damage may occur Important information Theinfosymbolindicatesimportantinformationwherethereisnoriskto people or property 1 2 General safety instructions H Notice for the target group These installation instructions are intended for plumbers heating engineers and electricians All instructions must be observed Failure to comply with instructions may result in materi...

Страница 4: ...2 control system User interface CR102 as a simple remote room controller User interface CR10H as a simple remote room controller with option to measure relative humidity heating cooling circuits MM 100 module for one heating cooling circuit with mixing valve MP 1002 module for a swimming pool MS 1002 module for solar DHW heating MS 2002 module for advanced solar systems Combination is not possible...

Страница 5: ...d confirm Mixer heating circuit 1 Yes No setting that defines whether heating circuit 1 is a heating circuit with mixer Mixer runtime heat circ 1 0 600 s setting that specifies the time required by the mixing valve in heating circuit 1 to turn from one stop to the other Heating system heat circ 1 Radiators Convector Floor setting for the type of heating distribution in the selected heating circuit...

Страница 6: ... system Press and hold the selector until a pop up menu is displayed Select Yes in the menu Switch from standby mode to normal operation To permanently shutdown Disconnectpower from the entire system and all BUS nodes After a prolonged power failure or extended period of idleness the date and time may need to be reset All other settings are retained permanently 3 8 Quick start of heat pump Open th...

Страница 7: ...rt time for the low noise operation Low noise operation until set the stop time for the low noise operation Min outside temp Below this outdoor temperature the heat pump switches over to normal operation Menu item Control range Function description Prim heating pump mode Automatic The primary circulation pump is in operation when any heat source is active When all heat sources are off the circulat...

Страница 8: ... increased DHW peak The energy available in the PV system is used for DHW Yes No If enabled the DHW is heated to the temperature set for DHWoperatingmode DHWcomfort Noheatingisdoneif the holiday program is active Cooling setback mode If Onlycoolwith PV is setto Yes sethowmany degrees the heat pump is allowed to lower the indoor temperature Only cool with PV Cooling mode is activated only if energy...

Страница 9: ... heater is allowed to start and the heat pump is blocked below the set outdoor temperature Alternating operation Bival pt switch mode2 Add heater DHW cylinder Yes No Choose if the DHW cylinder has an electric additional heater installed Menu item Control range Function description Is a buffer cylinder installed Yes No Set if a buffer cylinder is installed in the heating system Config HC1 at HP No ...

Страница 10: ...automatically changes from the setback mode to the heating mode Heat constantly below a certain outside temperature Frost prot Notice to ensure frost protection for the entire heating system set outside temperature dependent frost protection This setting is independent of the set control type Outdoor temp Room Room and outside temp frost protection is deactivated activated on the basis of the temp...

Страница 11: ...etectionisdeactivatedfortheselected heating circuit Menu item Adjustment range Design temperature or End point 30 75 85 C radiator convector 30 45 85 C underfloor heating system The design temperature is only available with weather compensated control without base point The design temperature is the flow temperature that is reached at the minimum outside temperature and therefore affects the steep...

Страница 12: ... protection outside temperature threshold is set It is only effective if Frost prot Outdoor temp or Room and outside temp is set in the menu NOTICE Domestichotwatercarryingpartsmaybedamagedbeyondrepairif thefrostprotectionlimittemperatureissettoolowandinprolonged periods with outside temperature below 0 C Only contractors are permitted to adjust the factory setting of the frost protection limit te...

Страница 13: ...ase Fig 6 2 Holding phase period 1 7 99 days time delay between the beginning of the holding phase duration of the maximum temperature for screed drying and the next phase Fig 6 4 Holding phase temp 20 55 C flow temperature during the holding phase maximum temperature Fig 6 4 Cool down phase incr No cool down phase no cooling phase takes place 1 10 days setting for the time delay between the steps...

Страница 14: ...ed by the heat source Circulation oper mode Off circulation off On circulation permanently on by taking the start frequency into account As DHW system Activate the same time program for circulation as for DHW heating Further information and settingsofthecustomisedtimeprogram userinterface operating instructions Own time program activate customised time program for circulation Further information a...

Страница 15: ...r 3 minutes as soon as there is a short tap 2 10 seconds The pump is then blocked for 10 minutes Automat therm disinfect Yes the thermal disinfection is started automatically at the set time No the thermal disinfection is not started automatically Therm disinfection day Monday Tuesday Sunday weekday on which thermal disinfection is performed Daily heat up thermal disinfection is performed daily Th...

Страница 16: ...in the system can be called up in this menu 4 9 6 Maintenance menu The contact address for a service company can be set in this menu The contactaddress is automatically displayed to the end user in case of a fault Entering company name and telephone number The current cursor position will flash marked by Turn the selector to move the cursor Press the selector to activate the input field Turn and p...

Страница 17: ...rvice providers and or Bosch affiliated enterprises In some cases but only if appropriate data protection is ensured personal data might be transferred to recipients located outside of the European Economic Area Further information are provided on request You can contact our Data Protection Officer under Data Protection Officer Information Security and Privacy C ISP Robert Bosch GmbH Postfach 30 0...

Страница 18: ...ture sensor in the controller in accordance with table If the sensor values matched but the voltage values do not match replace the control unit A01 811 and A41 4051 4052 DHW provision thermal disinfection unsuccessful Test procedure Cause Action A11 1038 Invalid time date Test procedure Cause Action Date time not yet set Set date time Prolonged loss of power supply Avoid voltage failures A11 3061...

Страница 19: ...ion Check parameter settings at the installation level Register room temperature dependent controller for heating circuit 1 4 as remote control Hxx Test procedure Cause Action For instance service interval of heat source elapsed Service required see documents for the heat source A01 5378 Outdoor unit defrost failure Test procedure Cause Action Too low temperature of heating system Open more thermo...

Страница 20: ...ogic ext connection 1 Block compr operation Block HW operation Block heating mode Block cooling mode Overheat protection HC1 ESC blocking time1 on ESC blocking time2 on ESC blocking time3 on Block additional heater PV system External connection 2 External connection 3 External connection 4 Fuse size Manual defrosting Smart grid Heating Selectable peak Forced peak DHW Selectable peak PV system Heat...

Страница 21: ... dry System Screed drying system Screed dry HC 1 4 Screed drying heating circuit 1 4 Start Interrupt Continue DHW settings DHW operation energy manager Switch on temp EM Switch off temperature EM DHW comfort Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay...

Страница 22: ...ion Start Time Save all settings Commissioning complete Diagnosis Function check Activating function checks Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Monit values Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Output limiter Fault displays System information Maintenance Reset Calibration SnapShot ...

Страница 23: ......

Страница 24: ... Cotswold Way Warndon Worcester WR4 9SW United Kingdom Tel 0330 123 9559 worcester bosch co uk 0330 123 3366 TECHNICAL SUPPORT RENEWABLE SUPPORT 0330 123 9229 CONTROLS AND CONNECTIVITY TEAM 0330 123 3641 0330 123 9339 0330 123 9779 0330 123 9119 0330 123 0166 0330 123 9669 ...

Отзывы: