Bosch HPC 410 Скачать руководство пользователя страница 14

Service menu

 

HPC 410 – 6721832682 (2021/02)

14

4.4

DHW settings

General DHW settings

The settings of the DHW systems can be adapted in this menu. These 
settings are only available if the system is designed and configured 
accordingly. Default temperature settings depend on the installed heat 
source.

CAUTION

Risk of scalding!

The maximum DHW temperature can be set above 60 °C and during 
thermal disinfection the DHW is heated to above 60 °C.

▶ Inform all people concerned and make sure that a mixing device is 

installed.

The DHW system is activated by default at delivery.

▶ If no DHW system is installed, deactivate DHW system in the 

commissioning or in the DHW menu.

Perform thermal disinfection to kill off pathogens (e.g. legionella) on a 
regular basis. In the case of larger DHW systems, there may be statutory 
requirements for thermal disinfection.

DHW settings menu

Table 17 Settings in the DHW menu

Menu item

Control range: Function description

DHW operation 
energy manager

[Switch-on temp. EM]: Set the switch on DHW-
temperature from the energy management system.

[Switch-off temperature EM]: Set the switch-off DHW-
temperature from the energy management system.

DHW comfort

[Switch-on temperature]
[15... 65] °C: start (minimum) temperature for the DHW in 
comfort mode (depending on the installed heat source).

[Switch-off temperature]
[15... 65] °C: stop (maximum) temperature for the DHW in 
comfort mode (depending on the installed heat source).

[Ramp-up delay]
[4... 

10

...36] h: Start delay for the DHW mode.

DHW Eco

[Switch-on temperature]
[15... 65] °C: start (minimum) temperature for the DHW in 
Eco mode (depending on the installed heat source).

[Switch-off temperature]
[15... 65] °C: stop (maximum) temperature for the DHW in 
Eco mode (depending on the installed heat source).

[Ramp-up delay]
[4... 

30

...36] h: Start delay for the DHW mode.

DHW Eco+

[Switch-on temperature]
[15... 65] °C: start (minimum) temperature for the DHW in 
Eco+ mode (depending on the installed heat source).

[Switch-off temperature]
[15... 65] °C: stop (maximum) temperature for the DHW in 
Eco+ mode (depending on the installed heat source).

[Ramp-up delay]
[4... 

48

...50] h: Start delay for the DHW mode.

DHW circ. pump

[DHW circ.pump installed]: if a DHW circulation pump is 
installed and to be controlled by the heat source, the DHW 
circulation pump must be activated here as well.

[

Off

]: the DHW circulation pump cannot be controlled by 

the heat source.

Circulation oper. 
mode

[Off]: circulation off.

[

On

]: circulation permanently on (by taking the start 

frequency into account).

[As DHW system]: Activate the same time program for 
circulation as for DHW heating. Further information and 
settings of the customised time program (

user interface 

operating instructions).

[Own time program]: activate customised time program 
for circulation. Further information and settings of the 
customised time program (

user interface operating 

instructions).

DHW circ. start 
freq.

If the DHW circulation pump is active via the time program 
for the DHW circulation pump or if it is permanently 
switched on (DHW circulation pump operating mode: 
[On]), this setting affects the DHW circulation pump 
operation.

[1 x 3 minutes/h] ...[

3 x 3 minutes/h

]... 

[6 x 3 minutes/h]: the DHW circulation pump goes into 
operation once ... 6 times per hour for 3 minutes.

[Permanent]: the DHW circulation pump is permanently in 
operation.

Autom. therm. 
disinfect.

[Yes]: the thermal disinfection is started automatically at 
the set time. If a solar system is installed, the thermal 
disinfection must also be activated for this (

Technical 

documentation [MS 100] or [MS 200]).

[

No

]: the thermal disinfection is not started automatically.

Therm. 
disinfection day

[Monday] ... [

Tuesday

] ... [Sunday]: weekday on which 

thermal disinfection is performed.

[Daily heat-up]: thermal disinfection is performed daily.

Therm. 
disinfection time

[00:00 ... 

02:00

 ... 23:45]: time of day for the start of 

thermal disinfection at the set day.

Therm. 
disinfection temp.

[60 ...

65

...80] °C: temperature to which the DHW volume 

is heated during thermal disinfection.

Maximum duration [60 min...

180

...240] min: Maximum duration of the 

thermal disinfection.

Heat maint. time

[0 h...

1

...6] h: Time during which the temperature is held 

at thermal disinfection.

Daily heat-up

[Yes]: The DHW volume is automatically heated up daily at 
the same time to 60 °C.

[

No

]: No daily heat-up.

Daily heat-up time

[00:00 ... 

02:00

 ... 23:45]: time for the start of the daily 

heat-up.

DHW alternating 
operation

[

Yes

]: If a simultaneous heat requirement from the heating 

system and the DHW system are present, the heat source 
will alternating supply the heating system or DHW based on 
set times.

[No]: DHW heating has the higher priority and interrupts 
heating mode, if necessary.

[Prioritise DHW for]: 
[0...

30

...120] min: Duration of DHW heating.

[Heating priority for]: 
[5...

20

...120] min: Duration of heating mode.

Heat. circ. p. on, 
DHW op.

[

Yes

] | [No]: Set if all heating circulation pumps should run 

when DHW heating is active.

Menu item

Control range: Function description

Содержание HPC 410

Страница 1: ...6721832682 2021 02 Installation instructions for contractors User interface HPC 410 EMS 2 0010031776 002 ...

Страница 2: ...s for the heat pump 6 4 1 1 Menu Heat pump 6 4 1 2 Menu Pumps 7 4 1 3 Menu External connections 7 4 1 4 Menu Smart grid 8 4 1 5 Menu PV system 8 4 2 Additional heater settings 8 4 2 1 Menu Set additional heater 8 4 2 2 Menu Electric auxiliary heater 8 4 2 3 Menu Auxiliary heater with mixer 9 4 3 Heating settings 9 4 3 1 System data 9 4 3 2 Menu Priority heating circuit 1 10 4 3 3 Menu heating circ...

Страница 3: ...CE NOTICE indicates that material damage may occur Important information Theinfosymbolindicatesimportantinformationwherethereisnoriskto people or property 1 2 General safety instructions H Notice for the target group These installation instructions are intended for plumbers heating engineers and electricians All instructions must be observed Failure to comply with instructions may result in materi...

Страница 4: ...2 control system User interface CR102 as a simple remote room controller User interface CR10H as a simple remote room controller with option to measure relative humidity heating cooling circuits MM 100 module for one heating cooling circuit with mixing valve MP 1002 module for a swimming pool MS 1002 module for solar DHW heating MS 2002 module for advanced solar systems Combination is not possible...

Страница 5: ...d confirm Mixer heating circuit 1 Yes No setting that defines whether heating circuit 1 is a heating circuit with mixer Mixer runtime heat circ 1 0 600 s setting that specifies the time required by the mixing valve in heating circuit 1 to turn from one stop to the other Heating system heat circ 1 Radiators Convector Floor setting for the type of heating distribution in the selected heating circuit...

Страница 6: ... system Press and hold the selector until a pop up menu is displayed Select Yes in the menu Switch from standby mode to normal operation To permanently shutdown Disconnectpower from the entire system and all BUS nodes After a prolonged power failure or extended period of idleness the date and time may need to be reset All other settings are retained permanently 3 8 Quick start of heat pump Open th...

Страница 7: ...rt time for the low noise operation Low noise operation until set the stop time for the low noise operation Min outside temp Below this outdoor temperature the heat pump switches over to normal operation Menu item Control range Function description Prim heating pump mode Automatic The primary circulation pump is in operation when any heat source is active When all heat sources are off the circulat...

Страница 8: ... increased DHW peak The energy available in the PV system is used for DHW Yes No If enabled the DHW is heated to the temperature set for DHWoperatingmode DHWcomfort Noheatingisdoneif the holiday program is active Cooling setback mode If Onlycoolwith PV is setto Yes sethowmany degrees the heat pump is allowed to lower the indoor temperature Only cool with PV Cooling mode is activated only if energy...

Страница 9: ... heater is allowed to start and the heat pump is blocked below the set outdoor temperature Alternating operation Bival pt switch mode2 Add heater DHW cylinder Yes No Choose if the DHW cylinder has an electric additional heater installed Menu item Control range Function description Is a buffer cylinder installed Yes No Set if a buffer cylinder is installed in the heating system Config HC1 at HP No ...

Страница 10: ...automatically changes from the setback mode to the heating mode Heat constantly below a certain outside temperature Frost prot Notice to ensure frost protection for the entire heating system set outside temperature dependent frost protection This setting is independent of the set control type Outdoor temp Room Room and outside temp frost protection is deactivated activated on the basis of the temp...

Страница 11: ...etectionisdeactivatedfortheselected heating circuit Menu item Adjustment range Design temperature or End point 30 75 85 C radiator convector 30 45 85 C underfloor heating system The design temperature is only available with weather compensated control without base point The design temperature is the flow temperature that is reached at the minimum outside temperature and therefore affects the steep...

Страница 12: ... protection outside temperature threshold is set It is only effective if Frost prot Outdoor temp or Room and outside temp is set in the menu NOTICE Domestichotwatercarryingpartsmaybedamagedbeyondrepairif thefrostprotectionlimittemperatureissettoolowandinprolonged periods with outside temperature below 0 C Only contractors are permitted to adjust the factory setting of the frost protection limit te...

Страница 13: ...ase Fig 6 2 Holding phase period 1 7 99 days time delay between the beginning of the holding phase duration of the maximum temperature for screed drying and the next phase Fig 6 4 Holding phase temp 20 55 C flow temperature during the holding phase maximum temperature Fig 6 4 Cool down phase incr No cool down phase no cooling phase takes place 1 10 days setting for the time delay between the steps...

Страница 14: ...ed by the heat source Circulation oper mode Off circulation off On circulation permanently on by taking the start frequency into account As DHW system Activate the same time program for circulation as for DHW heating Further information and settingsofthecustomisedtimeprogram userinterface operating instructions Own time program activate customised time program for circulation Further information a...

Страница 15: ...r 3 minutes as soon as there is a short tap 2 10 seconds The pump is then blocked for 10 minutes Automat therm disinfect Yes the thermal disinfection is started automatically at the set time No the thermal disinfection is not started automatically Therm disinfection day Monday Tuesday Sunday weekday on which thermal disinfection is performed Daily heat up thermal disinfection is performed daily Th...

Страница 16: ...in the system can be called up in this menu 4 9 6 Maintenance menu The contact address for a service company can be set in this menu The contactaddress is automatically displayed to the end user in case of a fault Entering company name and telephone number The current cursor position will flash marked by Turn the selector to move the cursor Press the selector to activate the input field Turn and p...

Страница 17: ...rvice providers and or Bosch affiliated enterprises In some cases but only if appropriate data protection is ensured personal data might be transferred to recipients located outside of the European Economic Area Further information are provided on request You can contact our Data Protection Officer under Data Protection Officer Information Security and Privacy C ISP Robert Bosch GmbH Postfach 30 0...

Страница 18: ...ture sensor in the controller in accordance with table If the sensor values matched but the voltage values do not match replace the control unit A01 811 and A41 4051 4052 DHW provision thermal disinfection unsuccessful Test procedure Cause Action A11 1038 Invalid time date Test procedure Cause Action Date time not yet set Set date time Prolonged loss of power supply Avoid voltage failures A11 3061...

Страница 19: ...ion Check parameter settings at the installation level Register room temperature dependent controller for heating circuit 1 4 as remote control Hxx Test procedure Cause Action For instance service interval of heat source elapsed Service required see documents for the heat source A01 5378 Outdoor unit defrost failure Test procedure Cause Action Too low temperature of heating system Open more thermo...

Страница 20: ...ogic ext connection 1 Block compr operation Block HW operation Block heating mode Block cooling mode Overheat protection HC1 ESC blocking time1 on ESC blocking time2 on ESC blocking time3 on Block additional heater PV system External connection 2 External connection 3 External connection 4 Fuse size Manual defrosting Smart grid Heating Selectable peak Forced peak DHW Selectable peak PV system Heat...

Страница 21: ... dry System Screed drying system Screed dry HC 1 4 Screed drying heating circuit 1 4 Start Interrupt Continue DHW settings DHW operation energy manager Switch on temp EM Switch off temperature EM DHW comfort Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay DHW Eco Switch on temperature Switch off temperature Ramp up delay...

Страница 22: ...ion Start Time Save all settings Commissioning complete Diagnosis Function check Activating function checks Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Monit values Heat pump Heating circuit 1 4 DHW settings Ventilation Pool Solar Output limiter Fault displays System information Maintenance Reset Calibration SnapShot ...

Страница 23: ......

Страница 24: ... Cotswold Way Warndon Worcester WR4 9SW United Kingdom Tel 0330 123 9559 worcester bosch co uk 0330 123 3366 TECHNICAL SUPPORT RENEWABLE SUPPORT 0330 123 9229 CONTROLS AND CONNECTIVITY TEAM 0330 123 3641 0330 123 9339 0330 123 9779 0330 123 9119 0330 123 0166 0330 123 9669 ...

Отзывы: