If no faults are detected, the functionality of the FAS-420-TM and/or the airflow sensor is
checked using the test pipe or diagnostic software (see
Section 6.7 Functional Test of Airflow
Sensors
).
If the airflow malfunctions are not displayed on the fire panel, proceed as follows:
Check whether…
–
the FAS-420-TM was programmed in the central fire panel program and the program was
transferred
–
the transmission path between the FAS-420-TM and the fire panel is working correctly.
If no faults are detected, the functionality of the FAS-420-TM and/or the airflow sensor is
checked using the test pipe or diagnostic software (see
Section 6.7 Functional Test of Airflow
Sensors, page 81
).
6.7
Functional Test of Airflow Sensors
Check the functionality using a test pipe and a digital precision pressure gauge and with the
aid of a PC and the FAS-ASD-DIAG Diagnostic Software.
A full functional test using the digital precision pressure gauge is described below. A limited
functional test can also be carried out without a digital precision pressure gauge.
6.7.1
Preparations for the Functional Test
1.
Select the following settings using the programming software (see
Section 4.4.3 Parameter Settings via Programming Software, page 63
):
2.
Disconnect the pipe system from the FAS-420-TM.
Sensitivity
0.5%/m
Activation threshold for airflow malfunction
Alarm delay
30%
10 sec
Airflow Fault Delay
Fan voltage
LOGIC×
SENS
filter
30 sec
9 V
on
NOTICE!
Once the pipe system has been disconnected from the FAS-420-TM, the device reports a
malfunction when the set airflow malfunction delay has lapsed. If no airflow malfunction is
detected, the device is faulty.