FAS-420-TM Aspirating Smoke Detector
Installation of the Pipe System | en
67
Bosch Sicherheitssysteme GmbH
Operation Guide
F.01U.088.878 | 4.1 | 2010.11
5.
Close open pipe ends with an end cap.
NOTICE!
Do not use pipe clips with rubber inserts since these do not allow length extensions and the
pipe system could thus bend or even tear.
NOTICE!
On completion, test the pipe system:
–
For tightness
–
For fault-free connections
–
For correct planning of the air sampling openings.
Содержание FAS-420-TM
Страница 1: ...FAS 420 TM Aspirating Smoke Detector FAS 420 TM en Operation Guide ...
Страница 2: ......
Страница 103: ......