74
en | Installation of the Pipe System
FAS-420-TM Aspirating Smoke Detector
F.01U.088.878 | 4.1 | 2010.11
Operation Guide
Bosch Sicherheitssysteme GmbH
FAS-ASD-WS Water Separator
The FAS-ASD-WS Water Separator must be fitted at the lowest point in the pipe system
downstream of the air filter and the aspirating smoke detector (see
Figure 5.9
).
Connection
Attach two 45° pipe elbows on both sides (
not
supplied as standard) in order to achieve the
optimum distance from the wall for mounting the brackets. When installing, note the correct
direction of flow (see arrow on plastic container).
Also fasten the water separator with two screws and the clamp.
To empty, open the drain valve (see
Section 7.12 Maintenance Intervals, page 92
).
5.9
Test Adapter
For test purposes, the pipe system connection is simply pulled out and the test pipe
connected directly to the aspirating smoke detector. However, this is not possible if the
aspiration pipe system has to be permanently mounted. A test adapter should be used for this
application.
Figure 5.9
Installing the FAS-ASD-WS Water Separator in the pipe
system
1
Water separator
2
Pipe system connection
3
45° pipe elbow
1
2
3
3
FAS
-42
0-TM s
eries
Figure 5.10
Installing the test adapter in the pipe system
1 Test Adapter
2 Pipe system connection
FA
S-4
20-
TM
seri
es
1
2