FAS-420-TM Aspirating Smoke Detector
Appendix | en
99
Bosch Sicherheitssysteme GmbH
Operation Guide
F.01U.088.878 | 4.1 | 2010.11
8.4
Test Log for Aspirating Smoke Detectors in the FAS-420-TM
Series
Device number
Serial number of detector module
Serial number of housing base
---
Measurement value/set value
Commissioning
Visual check
+/-
Negative pressure
[Pa]
Sensitivity
[%/m]
Alarm delay
[s]
Air flow range
[10-50%]
Fault delay
[min]
Malfunction saving
[yes/no]
Dynamic air flow
[yes/no]
Localization
[yes/no]
LOGIC·
SENS
[yes/no]
Air-Pressure-Dependent Calibration
[yes/no]
Air-pressure-
in
dependent calibration
[yes/no]
Height
[m above sea
level]
Air pressure
[hPa]
Fan voltage
[9-13.5 V]
Airflow
[m/sec]
Temperature
[°C]
Obstruction malfunction
LED flashes
+/-
Relay fails after delay
+/-
Signal transmission to fire panel
+/-
Cause eliminated, LED off
+/-
Relay activates after drop below threshold
+/-
Cause eliminated, LED saved
+/-
Relay remains off for min. 100 secs
+/-
Breakage malfunction
LED flashes
+/-
Relay fails after delay
+/-
Signal transmission to fire panel
+/-
Cause eliminated, LED off
+/-
Relay activates after drop below threshold
+/-
Cause eliminated, LED saved
+/-
Relay remains off for min. 100 secs
+/-
Main alarm
LED flashes
+/-
Relay activates after delay
+/-
Signal transmission to fire panel
+/-
LED saved
+/-
Relay saved
+/-
Localization
Blow-out time
[10-255 secs]
Blow out fan
[9-13.5 V]
Intake fan
[9-13.5 V]
LED localization permanently at air sampling
opening A
[yes/no] /
[sec]