Maintenance and Service
In Germany, maintenance work and inspection work on security systems are governed by the
regulations of DIN VDE 0833; these regulations stipulate reference to the manufacturer’s
instructions for maintenance intervals.
–
Maintenance and inspection work should be carried out regularly and by trained
personnel.
–
BOSCH ST recommends carrying out a functional and visual inspection at least once a
year.
Testing
Detector Type
FAP-425-DO-R,
FAP-425-O-R,
FAP-425-O
FAH-425-T-R
FAP-425-DOT-
R,
FAP-425-OT-R,
FAP-425-OT
FAP-425-DOTC-R
Check of the LED display
X
X
X
X
Visual check of the mounting
X
X
X
X
Visual check for damage
X
X
X
X
Check the monitoring range has not
been restricted, for instance by
shelves or similar installations.
X
X
X
X
Triggering with hot air
-
X
X
X
Triggering with Test Aerosol
X
-
X
X
Triggering with CO Testing gas
-
-
-
X
–
With the FAP-425-DOTC-R, the gas sensor has a life cycle of max. 6 years. Once the gas
sensor has been switched off, this detector continues to function as a DOT or DO
detector and is displayed on the panel with "EMERGENCY OPERATION".
This is why multisensor detectors with C sensors need to be exchanged every 5-6
years.
–
Optical fire detectors should, depending on the environmental conditions, be cleaned and
exchanged regularly.
In especially dusty environments, cleaning and exchange may be necessary earlier.
Every detector has a Chamber Maid Plug
(cleaning opening with a plug) for blowing out
the optical chamber with compressed air (not
required for the Heat Detector).
Detector Type Encoding
With the exception of the FAP-425-O-R and FAP-425-O, all detectors are fitted with a colored
ring around the central individual display to identify the detector type.
7
7.1
30
en | Maintenance and Service
AVENAR detector 4000
2014.11 | 1.1 | F.01U.283.550
Operation Guide
Bosch Sicherheitssysteme GmbH