Selectable installation locations in
the programming software
(FSP‑5000‑RPS)
Detector Type
Sensitivity
Thermom
ax (T
max
)
Optical
(O)
Chemical
(C)
Production location
O, T
max
, T
diff
, C
Low (B)
Low*
Medium
Garage
O, T
max
, T
diff
, C
High (A2)
Low*
Low
High storage warehouse without
vehicle traffic with combustion
engine
O, T
max
, T
diff
, C
Low (B)
High
High
Conference hall/waiting room/
fairground
O, T
max
, T
diff
, C
High (A2)
Low*
Medium
Kitchen/casino/restaurant during
active operation
O, T
max
, C
Low (B)
Low*
Low
Warehouse with vehicle traffic
O, T
max
, T
diff
, C
Low (B)
Low*
Low
Rate of rise only (optical sensor off)
T
max
, T
diff
High (A2)
-
-
Optical only (thermal sensor off)***
O
-
Low
-
Fixed temperature heat only (optical
sensor off)
T
max
High (A2)
-
-
Optical/chemical (thermal sensor
off)***
O, C
-
Low
High
Schools/kindergarten
O, T
max
, T
diff
, C
High (A2)
Medium
High
Theater/concert hall
O, T
max
, T
diff
, C
High (A2)
Medium
High
O = optical sensor
T
max
= thermal maximum unit
T
diff
= thermal differential unit
C = chemical sensor
* If optical sensor sensitivity is low, the detector will only trigger if smoke as well as an
increase in CO concentration or temperature is detected.
*** For FAP-425-DOTC-R: does not comply with EN54-7
For details on installation height, see FAH‑425‑T‑R, page 17
FAP‑425‑DOT‑R / FAP‑425‑OT‑R / FAP‑425‑OT
Notice!
The default setting of the FAP-425-DOT-R, FAP-425-OT-R and FAP-425-OT detector types in
RPS is "Office (day mode)". For a description of this setting, see the below table.
4.2
AVENAR detector 4000
Programming | en
15
Bosch Sicherheitssysteme GmbH
Operation Guide
2014.11 | 1.1 | F.01U.283.550