Temperature
rate-of-rise [K
min
-1
]
Response time for detectors in the
sensitivity class A1R
Response time for detectors in the
sensitivity classes A2R/BR
Lower limiting
value [min/sec]
Upper limiting
value [min/sec]
Lower limiting
value [min/sec]
Upper limiting
value [min/sec]
10
1 min
4 min 20 s
2 min
5 min 30 s
20
30 s
2 min 20 s
1 min
3 min 13 s
30
20 s
1 min 40 s
40 s
2 min 25 s
18
en | Programming
AVENAR detector 4000
2014.11 | 1.1 | F.01U.283.550
Operation Guide
Bosch Sicherheitssysteme GmbH