Error handling instructions for Split outdoor unit
Split ODU – 6 720 817 722 (2015/06)
25
2.13
Error codes 52, 53
Fig. 22 Error codes 52, 53
2.13.1 Error code 52
Inverter PCB
Main/ODU PCB
CANboard
Installerboard
CH52
No Error
1
2
3
CH53
??
Situation
Description
Error code that is sent to
Installerboard by CAN
Waiting time of
communication before
error is generated
1
No communication between
INV-PCB and ODU-PCB
(380V / 3~units)
CAN-PCB receives error
code from ODU-PCB but
Inverter-PCB does not
respond
52
30 seconds
2
No communication between
ODU-PCB and CAN-PCB
CAN-PCB does not receive
signals from ODU-PCB
53
10 seconds
3
No communication between
CAN-PCB and Installerboard
CAN-PCB does not send
signals to Installerboard
55
ODU shuts down after 1~3
seconds from recognizing
CAN communication error
Table 25 Error codes 52, 53
Display
code
Title
Cause of error
Check point & Normal
condition
52
PCB
communica
tion error
• Checking the
communicati
on state
between
main PCB
and inverter
PCB
1. Generation of noise
source interfering with
communication
Table 26 Error code 52
Is transmission LED
(Yellow) of inverter
compressor PCB on?
No
->
Is noise filter or fuse normal?
▶
NO:
Replace noise filter or fuse
-or-
▶
YES:
Replace inverter
compressor PCB
Yes
Is transmission cable
connected correctly?
No
->
1. Re-connect transmission cable
Yes
Is main PCB normal?
No
->
1. Replace main PCB
Yes
• Replace inverter
compressor PCB
Table 27 Error diagnosis and countermeasure chart