Error handling instructions for Split outdoor unit
Split ODU – 6 720 817 722 (2015/06)
14
2.6
Error code 26
2.6.1
Error diagnosis and countermeasure flow chart
Display
code
Title
Cause of error
Check point & Normal
condition
26
DC
compressor
position
• Compressor
starting
failure
1. Check the connection of
comp wire “U,V,W”
2. Malfunction of
compressor
3. Check the component of
“IPM”, detection parts
Table 11 Error code 26
Is installation condition
normal?
No
->
1. Check pipe clogging /
distortion
2. Check covering (Indoor /
Outdoor unit)
3. Check EEV connector
assembly condition / normal
operation
4. Check refrigerant pressure
-->Reassemble or manage if
abnormality found
Yes
Are the resistance
between each phase
and insulation
resistance of inverter
compressor normal?
No
->
1. Check resistance between
each terminal of compressor
2. Check insulation resistance
between compressor terminal
and pipe
--> Replace compressor if
abnormality is found
Yes
Is compressor wire
connection condition
normal?
No
->
1. Check inverter PCB assembly
U,V,W connector connection
condition
2. Check wire disconnection and
wiring
3. Check compressor terminal
condition condition (bad
contact)
--> Reassemble if abnormality is
found
Yes
Is inverter PCB
assembly normal?
No
->
1. Check inverter PCB assembly
IPM normality
--> Replace inverter PCB assembly
Yes
Recheck power and
installation condition
Table 12 Error diagnosis and countermeasure chart