Error handling instructions for Split outdoor unit
Split ODU – 6 720 817 722 (2015/06)
29
2.16
Error code 61
2.16.1 Error diagnosis and countermeasure flow chart
Inspecting condenser pipe sensor
1. Set multi-tester as resistance measurement mode.
2. Measure the resistance between rated speed compressor discharge
sensor connector pins.
3. Measure resistance value of 5k
10% (25 °C basis).
4. Check if the sensor insulation is damaged --> measure the resistance
between sensor connector pin and unit assembly pipe 1M
.
Fig. 27 CN-C/PIPE connector
[1]
CN-C/PIPE (Violet 3Pin connector)
Display
code
Title
Cause of error
Check point & Normal
condition
61
High
temperatur
e in
condenser
pipe
• Overload
operation
(outdoor fan
constraint,
screened,
blocked)
• Unit heat
exchanger
contaminate
d
• EEV
connector
displaced /
poor EEV
assembly
• Poor
condenser
pipe sensor
assembly /
broken
1. Check outdoor fan
constraint / screened /
flow structure
2. Check if refrigerant is
overcharged
3. Check the status of the
EEV assembly
4. Check the status of
sensor assembly
Table 32 Error code 61
Is the unit properly
installed?
No
->
1. Check fan locking
2. Remove blockings around heat
exchanger
3. Maintain distance between
unit and the wall
4. Check pipe folding and
abnormality
5. Check SVC lock
Yes
Is the refrigerant
properly charged?
No
->
1. Check if refrigerant is
overcharged
--> Adjust refrigerant volume
Yes
Is the EEV properly
assembled?
No
->
1. Check the status of PCB
(inverter) CN-EEV1 assembly
2. Check the status of EEV
assembly
--> Reassemble / replace if
abnormality is found
Yes
Is the condenser pipe
sensor normal?
No
->
1. Check the sensor assembly
status
2. Check if the sensor is burned:
measure resistance
-->5k
10% (25 °C basis)
Yes
Recheck power and
installation condition
Table 33 Error diagnosis and countermeasure chart