Error handling instructions for Split outdoor unit
Split ODU – 6 720 817 722 (2015/06)
32
2.18
Error code 67
2.18.1 Error diagnosis and countermeasure flow chart
Check point
1. Check voltage between 1pin and 4pin of fan motor connector (tester
diode mode).
2. Voltage value should be in 1V
0.2V.
3. Do not replace all of fan motor and 220 – 240 V~at once.
4. Check error code again, after replacing the abnormal part (fan motor
or PCB) first.
Fig. 30 Error code 67
[1]
Fan motor connector
Display code
Title
Cause of error
Check point & Normal condition
67
Fan lock error
• Fan RPM is 10 RPM or less for 5
seconds when ODU fan starts or
40 RPM or less after fan starting
1. ODU fan locking
2. Heat sink assembly of PCB assembly 1 condition abnormal
3. Defect of temperature sensing circuit part defect of PCB
(inverter)
Table 36 Error code 67
Is ODU fan motor
assembly condition
normal?
No
->
1. Check ODU fan motor
assembly condition and fan
locking
--> Reassemble or replace if
abnormality is found
Yes
Is ODU fan motor
normal?
No
->
1. Set the multi tester to diode
mode
2. Check voltage between 1pin
and 4pin of fan motor
(1
0.2V)
Yes
Is wire connection of
ODU fan motor wire
normal?
No
->
1. Check wiring between ODU fan
motor and PCB (inverter)
(Check if Hall sensor and
motor output terminal colour is
matched)
--> Reassemble if abnormality is
found
Yes
Is PCB assembly 1
normal?
No
->
1. Replace PCB assembly 1
Yes
Recheck power and
installation condition
Table 37 Error diagnosis and countermeasure chart
6 720 817 722-26.1I
1