Error handling instructions for Split outdoor unit
Split ODU – 6 720 817 722 (2015/06)
8
2.4
Error code 22
2.4.1
Error diagnosis and countermeasure flow chart
Check Point
1. Check the power source (230V
15%).
2. Check that the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the CT sensor output signal.
Display
code
Title
Cause of error
Check point & Normal
condition
22
Max. C/T
-Input Over
Current
1. Malfunction of
Compressor
2. Blocking of Pipe
3. Low Voltage Input
4. Refrigerant, Pipe length,
Blocked
Table 7 Error code 22
Is installation condition normal?
No
->
1. Check pipe clogging / distortion
2. Check covering (unit)
3. Check EEV connector assembly condition / normal
operation
4. Check refrigerant pressure
-> Reassemble or manage if abnormality found
Yes
Are the resistance between each phase
and insulation resistance of inverter
compressor normal?
No
->
1. Check resistance between each terminal of compressor
2. Check insulation resistance between compressor terminal
and pipe
-> Replace compressor if abnormality is found
Yes
Is compressor wire connection
condition normal?
No
->
1. Check connection between PCB assembly and bridge diode
(misconnection, disconnection)
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition (bad
contact)
-> Reassemble if abnormality is found
Yes
Is inverter PCB assembly 1 power
connection normal?
No
->
1. Check connection between PCB assembly 1 and bridge
diode (misconnection, disconnection)
-> Wiring again if abnormality is found
Yes
Is input voltage normal?
No
->
1. Check L~N phase is 230V
15%
-> Check connection condition and wiring if power is
abnormal
Yes
Is PCB assembly 1 normal?
No
->
1. Check PCB assembly 1 IPM normality
-> Replace inverter PCB assembly
Yes
Recheck power and installation
condition
Table 8 Error diagnosis and countermeasure chart