Installation
www.bora.com
6.5.4 Installation – standard set-up
1
2
3
4
5
6
7
Abb. 6.22 Standard set-up
[1]
Cooktop extractor
[2]
90° diverter
[3]
Horizontal tube bend
[4]
Silencer
[5]
Universal plinth fan
[6]
Air duct/recirculation unit
[7]
Universal control unit
X
X
Push the tube bend [3] onto the exhaust fitting of the
cooktop extractor [1].
X
X
Push the 90° diverter [2] onto the tube bend [3].
X
X
Position the plinth fan [5].
Q
Q
To facilitate positioning, the inlet nozzle on the plinth fan
can be removed. To do this, please see the assembly
instructions for the ULS25 universal plinth fan.
X
X
Connect the silencer [4] to the plinth fan [5].
X
X
Connect the silencer [4] to the 90° diverter [2].
X
X
Use the UDB25 sealing tape (not included in the scope
of delivery) to adhere together the connections for the
ducting sections with an air tight join.
Q
Q
You can also optimally adhere together the connections
between the ducting sections and the plinth fan with
UDB25 sealing tape.
INFO
Position the plinth fan and the universal
control unit in such a way that they are easily
accessible and removable for maintenance
work.
Q
Q
The maximum exhaust air duct length with a fan is
6 m.
Q
Q
The minimum cross-section of the air ducts must
be 176 cm
2
, which equates to a round pipe with a
diameter of 150 mm.
Abb. 6.20 Sealing tape position for installation with a round duct
Q
Q
Depending on the required connection cross-section,
you can vary the height at which the sealing tape is
attached to the plinth fan inlet nozzle.
X
X
Secure the sealing tape on the outlet nozzle.
Abb. 6.21 Sealing tape position for installation with a transition
piece (shallow duct)
INFO
When attaching the sealing tape, ensure that
an airtight seal with the connection duct piece
is created when the tape is compressed.