Installation

www.bora.com

X

X

If simultaneously operating both a fireplace and the 

cooktop extractor in the same room, ensure that:

Q

Q

the maximum low pressure is 4 Pa (4 x 10

–5

 bar);

Q

Q

a safety device (e.g. window contact switch, low 

pressure warning device) is used to ensure that a 

sufficient supply of fresh air is guaranteed;

Q

Q

the exhaust air is not be ducted into a chimney that 

is used for exhaust gases of devices operated with 

gas or other combustibles;

Q

Q

the installation is checked and approved by an 

authorised certified engineer (e.g. heating engineer).

6.6  Establishing the power 

connection and communication

X

X

Observe all safety and warning information  

(see the Safety section).

X

X

Observe all national and regional laws and regulations 

as well as the supplementary regulations of the local 

utility companies.

Q

Q

The plug for the power supply must be accessible  

following installation.

Q

Q

If the power supply cable has been damaged this must 

be replaced.

Connecting the universal control unit and fan 

to the cooktop extractor control box

8

6

4

2

1

7

5

3

Abb. 6.25 Connections on the universal control unit

[1] 

CAT 5 communication cable

[2] 

Home-Out

[3] 

Home-In

[4] 

Fan 1 control line

[5] 

Fan 2 control line

[6] 

Fan 1 power supply cable

[7] 

Fan 2 power supply cable

[8] 

Power supply cable with microfuse

Q

Q

For the ducting, only use stable duct elements with 

smooth pipe interiors. Do not use flexible or fabric 

tubes.

Q

Q

The exhaust air must be directed outside or to the 

recirculation unit through appropriate ducts.

Q

Q

For further planning examples and notices, please see 

the ventilation handbook (not included in the scope of 

delivery).

Installing the additional fan

X

X

Install the additional fan in the exhaust duct.

X

X

Ensure that a minimum clearance of 300 cm is  

maintained between the fan units. 

X

X

Only use BORA universal fans with your BORA cooktop 

extractor system.

Operating the cooktop extractor with a  

fireplace that depends on the air in the room

INFO 

The state and regional laws and regulations 

must be observed with regard to the exhaust 

duct design. A sufficient air supply must be 

ensured.

Fireplaces that depend on the air in the room (e.g. gas, oil, 

wood or coal-fired heaters, continuous-flow water heaters, 

instantaneous water heaters) draw in air from the room 

in which they are installed and release the exhaust fumes 

into the outside air via an exhaust system (e.g. chimney).

If the cooktop extractor is used in exhaust mode, it draws 

in air from the room in which it is installed as well as from 

neighbouring rooms. If there is insufficient air supply, low 

pressure will occur. Toxic gases could be drawn out of the 

chimney or extraction ducting and back into the room.

Abb. 6.23 Exhaust air installation – not permitted

Abb. 6.24 Exhaust air installation – correct

Содержание PL540E

Страница 1: ...EN PL540EUMEN 000 www bora com Operating and installation instructions PL540E Cooktop extractor M8800359 000...

Страница 2: ...heimer Str 32 83064 Raubling Germany Contact T 49 0 8035 907 240 F 49 0 8035 907 249 info bora com www bora com The distribution and duplication of this document as well as the use and disclosure of i...

Страница 3: ...fitting on the left 18 6 5 3 Preparing for installation standard set up 19 6 5 4 Installation standard set up 20 6 6 Establishing the power connection and communication 21 6 7 Connecting external swit...

Страница 4: ...label Directive 2011 65 EC RoHS Directive 1 General Target group These operating and assembly instructions are intended for the following target groups Target group Requirements Users The Device may...

Страница 5: ...th symbols and signal words Safety and warning instructions are structured as follows WARNING SYMBOL AND SIGNAL WORD Type and source of the danger Results of non compliance XMeasures to minimise risk...

Страница 6: ...while doing so XDo not use a steam cleaner for cleaning Steam can cause a short circuit on live parts and thus lead to property damage see the Cleaning chapter 2 Safety 2 1 General safety precautions...

Страница 7: ...miliar with and comply with common national regulations and supplementary regulations of the local utility companies XDo not place any hot cookware in the area of the control panel so as not to damage...

Страница 8: ...ock XSafely disconnect the device from the mains using miniature or automatic circuit breakers fuses or contactors XUse a suitable measuring device to ensure that the device is de energised Work on el...

Страница 9: ...ersons or damage to device Modifications attachment parts or conversions to device can impair safety XOnly use original spare parts when carrying out repairs 2 6 Use as intended The device is solely i...

Страница 10: ...umption 700 W Dimensions 110 x 540 x 167 mm Control box dimensions width x depth x height 96 x 85 x 76 mm Weight incl accessories packaging 5 kg Cooktop extractor Power levels 1 9 Tab 3 1 Technical da...

Страница 11: ...maximum Qmax 626 m h 61591 Sound power level Level 1 minimum 44 dB A 60704 2 13 Level 9 maximum 67 dB A 60704 2 13 Sound pressure level additional details Level 1 minimum 32 dB A Level 9 maximum 54 dB...

Страница 12: ...recircu lating air version Exhaust mode The air extracted from the cooktop is cleaned by the stainless steel grease filter and released outside through a duct system The exhaust air must not be expell...

Страница 13: ...for the signal input from external switch devices e g window contact switch Q Q The Home Out contact can be used to control external installations 5 3 6 Safety shut down The cooktop extractor switche...

Страница 14: ...l safety and warning information see the Safety section INFO The device must not be installed above cooling devices dishwashers stoves ovens washing machines or dryers INFO The contact surfaces of the...

Страница 15: ...out dimensions X X Adhere the supplied nameplate adhesive label to the back of your operating and installation instructions 6 4 Cut out dimensions Preparing the worktop X X Create the worktop cut out...

Страница 16: ...between the cooktops as well as between the cooktops and the cooktop extractor INFO Cable protection false floor should be mounted below the appliances This needs to be removable for maintenance work...

Страница 17: ...ixing nut 5 to the mounting bracket and tighten the fixing nut with max 10 Nm Abb 6 12 Tighten the fixing nut 6 5 1 Installing the control box behind the floor unit s fixed front panel 1 2 3 4 6 5 Abb...

Страница 18: ...l knob 6 X X Use the fixing screws provided to screw the control box onto the fixed front panel in a horizontal position from the inside This prevents the control box from twisting around Adjust the c...

Страница 19: ...ation X X Now adjust the ducting parts to the height of the worktop X X Saw out the necessary cut outs for the ducting in the rear panel of the floor unit X X Depending on the installation situation a...

Страница 20: ...e ducting sections with an air tight join Q Q You can also optimally adhere together the connections between the ducting sections and the plinth fan with UDB25 sealing tape INFO Position the plinth fa...

Страница 21: ...ble with microfuse Q Q For the ducting only use stable duct elements with smooth pipe interiors Do not use flexible or fabric tubes Q Q The exhaust air must be directed outside or to the recirculation...

Страница 22: ...ntact switches If the switch is open the cooktop extractor is out of operation X X Ensure that the universal control unit is disconnected from the power supply Preparing the universal control unit X X...

Страница 23: ...of 9 mm on the stripped wire end 1 Q Q Please adhere to the maximum stripping length of 26 mm on the insulated wire 2 1 2 4 3 Abb 6 28 Open the universal control unit s cover 1 Cover 2 Electronic uni...

Страница 24: ...g the external switch device Depending on the type of switch device connect the connection cables to either the Home In or the Home Out connection clamp X X Adhere to the connection diagram when conne...

Страница 25: ...operation see the Safety section INFO The cooktop extractor must only be operated with BORA cooktops INFO The cooktop extractor only works if the cover flap is open INFO The cooktop extractor should o...

Страница 26: ...ted charcoal filter has expired with recirculation only and the stainless steel grease filter needs to be thoroughly cleaned The filter service display is shown every time the cooktop extractor is swi...

Страница 27: ...ng mechanism 8 Cleaning and Maintenance X X Observe all safety and warning information see the Safety section INFO Clean the stainless steel surfaces in the polishing direction only Q Q Regular cleani...

Страница 28: ...eel grease filter absorbs the greasy particles from cooking vapours Q Q If it is no longer possible to clean the stainless steel grease filter completely it must be replaced 8 2 3 Installing the cover...

Страница 29: ...The service life can be found in the operating instructions for the relevant activated charcoal filter INFO You can obtain activated charcoal filters from your specialist supplier or by contacting BO...

Страница 30: ...is switched off The Home In contact is broken When using a window contact switch safety device the window must be open when the fan is operating The safety device is defective Call BORA After Sales Se...

Страница 31: ...environmentally friendly way Disposal of transport packaging INFO The packaging protects the device against transport damages The packaging is made of materials that are environmentally friendly and e...

Страница 32: ...7 X X In the case of faults you cannot fix yourself contact your BORA specialist supplier or BORA After Sales Service The After Sales Service will require the type designation and the serial number of...

Страница 33: ...EN 33 Notes www bora com 12 Notes...

Страница 34: ...EN 34 Notes www bora com...

Страница 35: ......

Страница 36: ...ndorf Austria T 43 0 5373 62250 0 F 43 0 5373 62250 90 mail bora com www bora com Europe BORA Holding GmbH Prof Dr Anton Kathrein Stra e 3 6342 Niederndorf Austria T 43 0 5373 62250 0 F 43 0 5373 6225...

Отзывы: