8.1.3
Setting Request / Select Telegram
Via the select telegram, the data are sent to the frequency inverter.
Positioning request PLC
frequency inverter:
Byte
0
1
2
3
4
5
6
7
8
9
…
n
Header
NoB SYS
DS
P.-No.
data
7
6
5…0
LSB
MSB
uint/int data
R/W 0
0
nn
nn
nn
nnnn
LSB
MSB
long data
LSB
MSB
string data
first
character
last
character
Header:
Bit 7 R/W
1 = Setting request
NoB:
Byte number
Number of relevant bytes
([Byte 2] … [Byte 5] + Number of data bytes)
SYS:
Addresses frequency inverters which are connected to a TCP/IP module via CAN System
Bus.
SYS = 0 for direct addressing of frequency inverter in Ethernet connection
DS:
Data set number of parameter (0,1 …, 4, 5, 6 … 9)
P. No.:
Parameter number (0 … 1599)
data:
parameter value to be written, byte number depending on data type
Setting response frequency inverter
PLC:
Byte
0
1
2
3
4
5
6
7
8
9
…
n
Header
NoB SYS
DS
P.-No.
data
7
6
5…0
LSB
MSB
uint/int data
R/W E
0
nn
nn
nn
nnnn
LSB
MSB
long data
LSB
MSB
string data
first
character
last
character
Header:
Bit 7 R/W
1 = Setting response
Bit 6 E
0 = no error
1 = error
if (E == 1)
byte 6+7 contains error code (
NoB = 6)
NoB:
Byte number
Number of relevant bytes
([Byte 2] … [Byte 5] + number of data bytes)
SYS:
returns value SYS from the request frame
DS:
returns dataset number from the request frame
P. No.:
returns parameter number from the request frame
data:
returns written parameter value, byte number depending on data type
12/13
Agile
VABus/TCP
37