7.5
Operating behavior in the case of a communication error
The operating behavior in the case of errors in VABus/TCP communication can be parameterized. The
required behavior can be set up via
Bus Error Behaviour
388.
Bus Error Behaviour
388
Function
0 - no response
Operating point is maintained.
1 - Error
“Fault” status will be activated immediately. Factory setting.
2 - Stop
Control command “Disable voltage” and switch to “switch on disa-
bled” status.
3 - Quick stop
Control command “Quick stop” and switch to “switch on disabled”
status.
4 - Sh Error
Control command “Disable operation” and switch to “Error” status
once the drive has been shut down.
5 - Quick stop + Error
Control command “Quick stop” and switch to “Error” status once
the drive has been shut down.
The parameter settings
Bus fault behavior
388 = 2…5 are evaluated depending on
parameter
Local/Remote
412.
For evaluation of settings 2…5, parameter
Local/Remote
412 must be set to value “1 -
Control via statemachine”.
12/13
Agile
VABus/TCP
33