BOGE Operating instructions for scroll compressors, series EO 6...EO 22 D
Page 25
Product description
3.4
Technical data
Technical data EO 11...EO 22 D, part 2
Technical data for DS dryer
Technical data for dryer DRL 6-2
Type
EO 11 / EO 11 D
EO 16
EO 17 / EO 17 D EO 22 / EO 22 D
Intake air temperature
– min.
[°C]
+5
+5
+5
+5
– max.
[°C]
+40
+40
+40
+40
Cooling air requirement
– Required ventilator output for compressor room
ventilation
[m
3
/h]
4900
6000
6000
7000
– Cooling air requirement
[m
3
/h]
2840
3500
3500
4300
– Free fan compression
[Pa]
20
20
20
20
– Free fan compression
[mm WS]
2
2
2
2
Operating pressure values
1
)
1)
For compressors for other operating pressures p
min
= p
max
– 1 bar.
(factory settings)
– p
max
= 8 bar: Switch-off pressure p
max
[bar]
8
8
8
8
Switch-on pressure p
min
[bar]
7
7
7
7
– p
max
= 10 bar: Switch-off pressure p
max
[bar]
10
10
10
10
Switch-on pressure p
min
[bar]
9
9
9
9
Safety valve on scroll unit
Response pressure at:
– p
max
= 8 bar
[bar]
12
12
12
12
– p
max
= 10 bar
[bar]
12
12
12
12
Model
of dryer
Compressor
type
Weight
approx.
Refrigerant
volume R134a /
CO
2
equivalent
approx.
Max.
operat-
ing
pressure
Max.
compressed air
inlet tempera-
ture
Cooling
air
require-
ment
Power
con-
sumption
Supply
voltage
[kg]
[kg / t]
[bar]
[°C]
[m
3
/h]
[kW]
[V]
DS 4-2
EO 6 DR 10 bar
24
0,16 / 0,23
16
65
90
0,15
230
DS 7-2
EO 6 DR 8 bar
24
0,16 / 0,23
16
65
90
0,14
230
DS 30
EO 17 D
EO 22 D
35
0,36 / 0,51
16
65
550
0,78
230
Model
of dryer
Compressor
type
Weight
approx.
Refrigerant
volume R134a /
CO
2
equivalent
approx.
Max.
operat-
ing
pressure
Max.
compressed air
inlet tempera-
ture
Cooling
air
require-
ment
Power
con-
sumption
Supply
voltage
[kg]
[kg / t]
[bar]
[°C]
[m
3
/h]
[kW]
[V]
DRL 6-2
EO 6 D
EO 11 D
35
0,34 / 0,49
16
60
550
0,22
230