background image

507324-01B

Page 16 of 32

Issue 1809

14.  All  venting  pipe  passing  through  floors,  walls,  and 

ceilings must be installed with the listed clearance to 

combustible materials and be fire stopped according 

to  local  codes.  In  absence  of  local  codes,  refer  to 

NFGC (2223.1 ).

15.  No portion of the venting system can extend into, or 

pass through any circulation air duct or plenum.

16.  Vent connectors serving Category I appliances  shall 

not be connected to any portion of mechanical draft 

systems  operating  under  positive  pressure  such  as 

Category III or IV venting systems.

17.  If vent connectors are combined prior to entering the 

common  vent,  the  maximum  common  vent  capacity 

listed in the common venting tables must be reduced 

by  10%,  the  equivalent  of  one  90°  elbow  (0.90  x 

maximum common vent capacity).

18.  The common vent diameter must always be at least as 

large as the largest vent connector diameter.

19.  In  no  case,  shall  the  vent  connector  be  sized  more 

than  two  consecutive  table  size  diameters  over  the 

size of the draft hood outlet or flue collar outlet.

20.  Do  not  install  a  manual  damper,  barometric  draft 

regulator  or  flue  restrictor  between  the  furnace  and 

the chimney.

21.  When  connecting  this  appliance  to  an  existing 

dedicated  or  common  venting  system,  you  must 

inspect  the  venting  system’s  general  condition  and 

look for signs of corrosion. The existing vent pipe size 

must conform to these instructions and the provided 

venting tables. If the existing venting system does not 

meet these requirements, it must be resized.

Содержание BG801UH

Страница 1: ...Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING As with any mechanical equipment personal injury can result from contact with sharp sheet metal edges Be careful when you handle this equi...

Страница 2: ...r filter 2 Single side return air with optional RAB Return Air Base 3 Bottom return air 4 Return air from both sides 5 Bottom and one side return air 2 Flue outlet may be horizontal but furnace must be vented vertically 3 Optional external side return air filter kit cannot be used with the optional RAB Return Air Base Consider sizing requirements for optional IAQ equipment before cutting side retu...

Страница 3: ... vestibule area In order to ensure proper unit operation combustion and ventilation air supply must be provided according to the current National Fuel Gas Code Vent installations must be consistent with the venting tables in this instruction and applicable provisions of local building codes This furnace is CSA International certified for installation clearances to combustible material as listed on...

Страница 4: ...ature rise must be set per the furnace rating plate e Supply and Return air ducts must be provided and sealed to the furnace Return air must be terminated outside of the space where furnace is installed f Return air temperature range between 60 F 16 C and 80 F 27 C must be maintained g MERV 11 or greater air filters must be installed in the system and must be regularly inspected and maintained e g...

Страница 5: ...fficient combustion air is not available the furnace or other appliances will operate inefficiently and unsafely Enough air must be provided to meet the needs of all fuel burning appliances and appliances such as exhaust fans which force air out of the house When fireplaces exhaust fans or clothes dryers are used at the same time as the furnace much more air is necessary to ensure proper combustio...

Страница 6: ...enclosure and one opening within 12 inches 305 mm of the bottom See Figure 2 Air from Outside If air from outside is brought in for combustion and ventilation the confined space must have two permanent openings One opening shall be within 12 inches 305 mm of the top of the enclosure and one opening within 12 inches 305 mm of the bottom These openings must communicate directly or by ducts with the ...

Страница 7: ... back of the furnace Doing so will adversely affect the operation of the safety control devices which could result in personal injury or death WARNING The gas furnace can be installed as shipped in either the upflow position or the horizontal position Select a location that allows for the required clearances that are listed on the unit nameplate Also consider gas supply connections electrical supp...

Страница 8: ...e and the platform to ensure that the furnace operates properly and safely The furnace is equipped with a removable bottom panel to facilitate installation Markings are provided on both sides of the furnace cabinet for installations that require side return air Cut the furnace cabinet at the maximum dimensions shown on Page 2 NOTE 20C and 20D units that require air volumes over 1800 cfm 850 L s mu...

Страница 9: ... and supply and return air plenums must be supported separately NOTE When the furnace is installed on a platform in a crawlspace it must be elevated enough to avoid water damage and to allow the evaporator coil to drain Figure 11 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets FRONT VIEW 1 Unit side return air Opening SIDE VIEW 3 1 4 83 1 23 584 Overall Maximum ...

Страница 10: ... living space Use screws and joint tape to seal the return air system to the furnace Inplatforminstallationswithbottomreturnair thefurnace should be sealed airtight to the return air plenum A door must never be used as a portion of the return air duct system The base must provide a stable support and an airtight seal to the furnace Allow absolutely no sagging cracks gaps etc The return and supply ...

Страница 11: ...hout the house by the furnace duct system In upflow applications the return air can be brought in through the bottom or either side of the furnace If a furnace with bottom return air is installed on a platform make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely Use fiberglass sealing strips caulking or equivalent sealing met...

Страница 12: ...h hose from barbed fitting on the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to free pressure switch wires Reinstall pressure switch on the other side of orifice plate and reconnect pressure switch hose Resecure pressure switch wires Either pull excess wires through the blower compartment and secure using supplied wire tie or coil excess wire and secure to th...

Страница 13: ...on instructions and the provided venting tables in these instructions The venting tables in this manual were extracted from the National Fuel Gas Code NFPA 54 ANSI Z223 1 and are provided as a guide for proper vent installation Proper application termination construction and location of vents must conform to local codes having jurisdiction In the absence of local codes the NFGC serves as the defin...

Страница 14: ...ot accommodate a listed metal liner either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting method must be found Insulation for the flexible vent pipe must be an encapsulated fiberglass sleeve recommended by the flexible vent pipe manufacturer SINGLE appliance venting of a fan assisted furnace into a tile lined masonry chimney interior or outside wall...

Страница 15: ...appliance vents The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area drafthood outlet area or flue collar area unless designed according to approved engineering methods 6 The entire length of single wall metal vent connector shall be readily accessible for inspection cleaning and replacement 7 Singleappliancev...

Страница 16: ...acity listed in the common venting tables must be reduced by 10 the equivalent of one 90 elbow 0 90 x maximum common vent capacity 18 The common vent diameter must always be at least as large as the largest vent connector diameter 19 In no case shall the vent connector be sized more than two consecutive table size diameters over the size of the draft hood outlet or flue collar outlet 20 Do not ins...

Страница 17: ...9 15 136 20 226 22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 50 229 62 351 15 34 58 46 124 59 217 73 337 20 48 52 55 116 69 206 84 322 30 0 0 100 0 213 0 374 0 587 2 9 81 13 166 14 283 18 432 5 21 77 28 160 36 275 45 421 10 27 70 37 150 48 262 59 ...

Страница 18: ... 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181 60 288 2 21 64 33 118 47 190 62 299 3 22 66 34 123 48 198 64 309 Table 4 Common Vent Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Applianc...

Страница 19: ...ance connected to the common venting system is venting properly step 3 return all doors windows exhaust fans fireplace dampers and any other gas burning appliances to their previous mode of operation 7 If a venting problem is found during any of the preceding tests the common venting system must be modified to correct the problem Resize the common venting system to the minimum vent pipe size deter...

Страница 20: ... 20 930 360 10 19 250 7 08 200 5 66 170 4 81 151 4 28 138 3 91 125 3 54 118 3 34 110 3 11 103 2 92 1 25 4 1 049 26 645 680 19 25 465 13 17 375 10 62 320 9 06 285 8 07 260 7 36 240 6 80 220 6 23 205 5 80 195 5 52 1 1 4 31 75 1 380 35 052 1400 39 64 950 26 90 770 21 80 660 18 69 580 16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 460 41 34 1180 33 41 990 28...

Страница 21: ...ures Electrostaticdischargecanaffectelectroniccomponents Take precautions during furnace installation and service to protect the furnace s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace the control and the technician at the same electrostatic potential Neutralize electrostatic charge by touching hand and all tools on an unpaint...

Страница 22: ... control See for integrated control configuration This terminal is energized when the indoor blower is operating Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals If an accessory rated at greater than one amp is connected to this terminal it is necessary to use an external relay One line ...

Страница 23: ...507324 01B Page 23 of 32 Issue 1809 045AP12 110CP20 110CP16 090BP16 070AP12 Figure 30 Wiring Diagram ...

Страница 24: ...mostat is set to FAN ON the indoor blower will run continuously on the heating speed when there is no cooling or heating demand 2 When the unit is running in the heating mode the indoor blower will run on the heating speed 3 When there is a cooling demand the indoor blower will run on the cooling speed NOTE This control is equipped with a push button switch for diagnostic code recall The control s...

Страница 25: ...l injury or death WARNING Gas Valve Operation See Figure 33 1 STOP Read the safety information at the beginning of this section 2 Set the thermostat to the lowest setting 3 Turn off all electrical power to the unit 4 This furnace is equipped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the upper access panel 6 Move switch on gas va...

Страница 26: ...4 After a 20 second ignitor warm up period the gas valve solenoid opens A 4 second trial for ignition period begins 5 Gas is ignited flame sensor proves the flame and the combustion process continues 6 If flame is not detected after first ignition trial the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve The ignition control will then automatically repea...

Страница 27: ...nd remove manometer as soon as an accurate reading has been obtained Take care to remove barbed fitting and replace threaded plug Proper Combustion Furnace should operate a minimum 15 minutes with correct manifold pressure and gas flow rate before checking combustion Take combustion sample beyond the flue out let and compare to the tables below The maximum carbon monoxide reading should not exceed...

Страница 28: ...umper position across the five pins on the integrated control The unit is shipped with a factory fan off delay setting of 90 seconds The fan off delay affects comfort and is adjustable to satisfy individual applications Adjust the fan off delay to achieve a supply air temperature between 90 and 110 F at the moment that the blower is de energized Longer off delay settings provide lower return air t...

Страница 29: ...an be drawn into living space resulting in personal injury or death WARNING Other Unit Adjustments Primary and Secondary Limits The primary limit is located on the heating compartment vestibule panel The secondary limits if equipped are located in the blower compartment attached to the back side of the blower These auto reset limits are factory set and require no adjustment Flame Rollout Switches ...

Страница 30: ...ecommended filter sizes Flue and Chimney 1 Check flue pipe chimney and all connections for tightness and to make sure there is no blockage 2 Check unit for proper draft Electrical 1 Check all wiring for loose connections 2 Check for the correct voltage at the furnace furnace operating Correct voltage is 120VAC 10 3 Check amp draw on the blower motor with inner blower panel in place Unit Nameplate_...

Страница 31: ...45 942 Med 1137 1131 1102 1080 1037 977 913 828 Low 958 956 943 925 879 837 777 725 090BP16 1 2 4 spd 10 x 10 30 60 High 1911 1840 1770 1663 1584 1469 1357 1198 Med High 1738 1707 1634 1560 1468 1364 1232 1121 Med 1533 1502 1462 1408 1329 1262 1157 1019 Low 1303 1304 1281 1225 1192 1116 1018 918 110CP16 1 2 4 spd 10 x 10 30 60 High 2078 2017 1939 1848 1775 1679 1559 1425 Med High 1791 1746 1693 16...

Страница 32: ...m height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not app...

Отзывы: