Clarity 26 FS IPI
FUEL CONVERSION
CONVERSION KIT CONTENTS
The conversion kit contains the following parts:
• S.Z0765 (LPG)> #635.OR1.5 (1.5 mm orifi ce), 635.977.168 (PF2 LP pilot orifi ce), and LPG regulator.
• S.Z0766 (NG)> #635.OR39 (#39 orifi ce), 635.977.166 (PF2 LP pilot orifi ce) and NG regulator.
• Conversion Kit labels.
To convert from NG to LPG or reverse:
1. Turn off the appliance and allow it to cool down completely
2. Remove burner (see
“BURNER REMOVAL”
on previous page)
3. Replace main orifi ces
4. Replace regulator
5. Convert pilot fuel (see next page).
All valves have been pre-set and certifi ed for installation at elevations from 0 – 4500 feet (1 – 1372m) above
sea level.
HIGH ELEVATIONS
When installing this unit at higher elevations, it is necessary to decrease the input rating by replacing the
existing burner orifi ce with a smaller size for installations over 4500 feet (1370 m). The appliances input should
be reduced 4% for each additional 1000 feet (305 m) above sea level. For the USA, de-rate the unit from sea
level according to the gas installation code.
MAINTENANCE and SERVICE cont.
THIS CONVERSION KIT SHALL BE INSTALLED BY A QUALIFIED SERVICE AGENCY IN
ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS AND ALL APPLICABLE CODES AND
REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. IF THE INFORMATION IN THESE
INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE, EXPLOSION OR PRODUCTION OF CARBON
MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF
LIFE. THE QUALIFIED SERVICE AGENCY IS RESPONSIBLE FOR THE PROPER INSTALLATION OF
THE KIT. THE INSTALLATION IS NOT COMPLETE UNTIL THE OPERATION OF THE CONVERTED
APPLIANCE IS CHECKED AS SPECIFIED IN THE INSTRUCTION MANUAL SUPPLIED WITH THE
KIT. BEFORE PERFORMING THIS OR ANY SERVICE PROCEDURE, MAKE SURE THAT THE GAS
SUPPLY TO THE UNIT AND THE ELECTRICAL SUPPLY ARE SHUT OFF.