D1014 

- SIL 2 Repeater Power Supply Hart compatible 

ISM0052-16 

D1014S - D1014D 

INSTRUCTION & SAFETY MANUAL 

SIL 2 Repeater Power Supply 

Hart compatible 

DIN-Rail Models D1014S, D1014D 

Содержание D1014S

Страница 1: ...D1014 SIL 2 Repeater Power Supply Hart compatible ISM0052 16 D1014S D1014D INSTRUCTION SAFETY MANUAL SIL 2 Repeater Power Supply Hart compatible DIN Rail Models D1014S D1014D...

Страница 2: ...uracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 05 of full scale for a min to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance ch...

Страница 3: ...locks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Not used Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for 2 wire Transmitters Input Ch 2 for 2 wi...

Страница 4: ...IB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and Li of...

Страница 5: ...SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1014D 14 15 3 4 1 2 RL mA mA V HHT Ch 1 Supply 12 24 Vdc Source I...

Страница 6: ...solver is configured to detect High failures and does not automatically trip on these failures this failure mode has been classified as a dangerous detected DD failure Fail Low failure mode that caus...

Страница 7: ...shed via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms o...

Страница 8: ...esponding section as an example Connect 12 24 Vdc power supply positive at terminal 3 and negative at terminal 4 for channel 1 For Model D1014D connect 12 24 Vdc power supply positive at terminal 7 an...

Страница 9: ...allows the mA sink or source mode or Volt operating mode configuration Configuration Side A Panel View Span Trimmer CH1 Screwdriver for Trimmers 1 x 0 5 mm Dip switch configuration Vtx Adjust Ch1 Scr...

Страница 10: ...ly is the same for all channels there for don t separate the terminals because one channel remains switched off Different power supply Cut both pins of the connector to open the wiring between the ter...

Страница 11: ...llow step 1 Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA mA mA MODEL D1014D 14 15 3 4 1 2 10 11 5 6 7 8 V V Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA MODEL D1014D...