D1014 

- SIL 2 Repeater Power Supply Hart compatible 

G.M. International ISM0052-16 

10 

Side B Panel View 

Calibration Trimmer Ch2 

Span Trimmer 

CH2 

Zero Trimmer 

CH2 

Vtx Adjust Ch2 

Screwdriver 

for Trimmers 

2 x 0.5 mm 

Screwdriver 

for Trimmers 

1 x 0.5 mm 

Terminal “3” and terminal “4” are internally connected to terminal “7” and terminal “8” for factory default. To supply the unit with different supply voltage or different power supply, open the 
wiring between the terminals (see the following figure); consult factory for detailed information. When using Power Bus enclosure the power supply is the same for all channels there for 
don’ t separate the terminals because one channel remains switched off. 

 

Different power supply 

Cut both pins of the connector to open the wiring between the terminals, using a wire cutter 

Turn the trimmer clockwise to Increase Output 

value or turn the trimmer counterclockwise if 
you want to decrease Output value. 

Turn the trimmer clockwise to 
Increase Output value or turn 

the trimmer counterclockwise 

if you want to decrease Output 

value. 

Channel 

Output Operation 

4-20 mA Source Mode (for SIL application) 

4-20 mA Sink Mode (for SIL application) 

1-5 V (on 250 

 internal shunt) 

Dip switch Configuration Summary Table 

SW1 

ON 

OFF 

ON 

SW2  SW3  SW4 

ON 

OFF 
OFF 

OFF 
OFF 

ON 

OFF 

ON 
ON 

SW5 

ON 

OFF 

ON 

SW6  SW7  SW8 

ON 

OFF 
OFF 

OFF 
OFF 

ON 

OFF 

ON 
ON 

Содержание D1014S

Страница 1: ...D1014 SIL 2 Repeater Power Supply Hart compatible ISM0052 16 D1014S D1014D INSTRUCTION SAFETY MANUAL SIL 2 Repeater Power Supply Hart compatible DIN Rail Models D1014S D1014D...

Страница 2: ...uracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 05 of full scale for a min to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance ch...

Страница 3: ...locks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Not used Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for 2 wire Transmitters Input Ch 2 for 2 wi...

Страница 4: ...IB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and Li of...

Страница 5: ...SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1014D 14 15 3 4 1 2 RL mA mA V HHT Ch 1 Supply 12 24 Vdc Source I...

Страница 6: ...solver is configured to detect High failures and does not automatically trip on these failures this failure mode has been classified as a dangerous detected DD failure Fail Low failure mode that caus...

Страница 7: ...shed via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms o...

Страница 8: ...esponding section as an example Connect 12 24 Vdc power supply positive at terminal 3 and negative at terminal 4 for channel 1 For Model D1014D connect 12 24 Vdc power supply positive at terminal 7 an...

Страница 9: ...allows the mA sink or source mode or Volt operating mode configuration Configuration Side A Panel View Span Trimmer CH1 Screwdriver for Trimmers 1 x 0 5 mm Dip switch configuration Vtx Adjust Ch1 Scr...

Страница 10: ...ly is the same for all channels there for don t separate the terminals because one channel remains switched off Different power supply Cut both pins of the connector to open the wiring between the ter...

Страница 11: ...llow step 1 Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA mA mA MODEL D1014D 14 15 3 4 1 2 10 11 5 6 7 8 V V Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA MODEL D1014D...

Отзывы: