background image

 

D1014 

- SIL 2 Repeater Power Supply Hart compatible 

G.M. International ISM0052-16 

General Description:

 The single and dual channel DIN Rail Repeater Power Supply, D1014S and D1014D is a high integrity analog input interface suitable for applications requiring 

SIL 2 level (according to IEC61508:2010 Ed. 2) in safety related system for high risk industries. Provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA 
transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load. The circuit allows bi-directional communication signals, for Hart transmitters. 

Function:

 1 or 2 totally independent and isolated channels I.S. analog input for 2 wires loop powered Hart transmitters, provides 3 port isolation (input/output/supply) and current 

(source or sink) or voltage output signal. 

Signalling LED:

 Power supply indication (green). 

Field Configurability:

 mA (source or sink) or V output signal. 

Hart Communication Frequency Band:

 0.5 to 2.5 KHz within 3 dB. 

EMC: 

Fully compliant with CE marking applicable requirements. 

 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. 

Supply:

 12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V: 

110 mA for 2 channels D1014D, 55 mA for 1 channel D1014S with 20 mA output typical. 

Current consumption @ 12 V: 

220 mA for 2 channels D1014D, 110 mA for 1 channel D1014S with 20 mA output typical. 

Power dissipation:

 1.8 W for 2 channels D1014D, 0.9 W for 1 channel D1014S with 24 V supply voltage and 20 mA output typical. 

Max. power consumption: 

at 30 V supply voltage and short circuit condition, 3.4 W for 2 channels D1014D, 1.7 W for 1 channel D1014S. 

Isolation (Test Voltage): 

I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V. 

Input:

 4 to 20 mA (2 wire Tx current limited at 

 25 mA). 

Transmitter line voltage:

 

 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 2.5 KHz frequency band. 

Output:

 4 to 20 mA, on max. 600 

 load in source mode; V min. 5 V at 0 

 load V max. 30 V in sink mode, current limited at 

 25 mA or 1 to 5 V on internal 250 

 shunt (or 2 to 10 V 

on internal 500 

 shunt on request). 

Response time:

 

20 ms (10 to 90 % step change). 

Output ripple:

 

 20 mVrms on 250 

 communication load on 0.5 to 2.5 KHz band. 

Frequency response:

 

0.5 to 2.5 KHz bidirectional within 3 dB (Hart protocol). 

Performance:

 Ref. Conditions 24 V supply, 250 

 load, 23 ± 1 °C ambient temperature. 

Calibration accuracy: 

 ± 0.1 % of full scale. 

Linearity error: 

 ± 0.1 % of full scale. 

Supply voltage influence: 

 ± 0.05 % of full scale for a min to max supply change. 

Load influence: 

 ± 0.05 % of full scale for a 0 to 100 % load resistance change. 

Temperature influence: 

 ± 0.01 % on zero and span for a 1 °C change. 

Compatibility: 

 
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions:

 

Operating:

 temperature limits -20 to + 60 °C, relative humidity max 95 %. 

Storage:

 

temperature limits – 45 to + 80 °C. 

Safety Description: 

ATEX:

 

II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I; II 3G Ex nA IIC T4 Gc 

IECEx / INMETRO:

 [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I; Ex nA IIC T4 Gc 

UL:

 AIS / I, II, III / 1 / ABCDEFG, [AEx ia] IIC 

C-UL:

 AIS / I, II, III / 1 / ABCDEFG, [Ex ia] IIC 

FM:

 NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx [ia] IIC 

FM-C:

 NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex [ia] IIC 

EAC-EX:

 2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC X, [Ex ia Ma] I X 

UKR TR n. 898:

 2ExnAiaIICT4 X, ExiaI X 

associated apparatus and non-sparking electrical equipment. 

Uo/Voc = 25.2 V, Io/Isc = 93 mA, Po/Po = 585 mW at terminals 14-15, 10-11. 

Um = 250 Vrms, -20 °C 

 Ta 

 60 °C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26. 

IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26. 

IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15. 

IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15. 

INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26, ABNT NBR IEC 61241-11. 

UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15 ANSI/ISA 12.12.01 for UL and 

CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11, CSA-C22.2 No. 213 and CSA-E60079-15 for C-UL. 

FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810, ANSI/ISA 12.12.02, ANSI/ISA 60079-0, ANSI/ISA 60079-11, 

C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15 

GOST R 12.2.007.0-75, R 51330.0-99, R 51330.10-99  

GOST 12.2.007.0,22782.0,22782.5  

TÜV Certificate No. C-IS-236198-03, SIL 2 conforms to IEC61508:2010 Ed.2. 

TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

DNV No.A-13625 and KR No.MIL20769-EL001 Certificates for maritime applications . 

Mounting:

  

T35 DIN Rail according to EN50022. 

Weight:

 

about 170 g D1014D, 115 g D1014S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 

Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA 

T4 installation. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

Characteristics 

FSM

SIL 3

Содержание D1014S

Страница 1: ...D1014 SIL 2 Repeater Power Supply Hart compatible ISM0052 16 D1014S D1014D INSTRUCTION SAFETY MANUAL SIL 2 Repeater Power Supply Hart compatible DIN Rail Models D1014S D1014D...

Страница 2: ...uracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 05 of full scale for a min to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance ch...

Страница 3: ...locks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Not used Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for 2 wire Transmitters Input Ch 2 for 2 wi...

Страница 4: ...IB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and Li of...

Страница 5: ...SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1014D 14 15 3 4 1 2 RL mA mA V HHT Ch 1 Supply 12 24 Vdc Source I...

Страница 6: ...solver is configured to detect High failures and does not automatically trip on these failures this failure mode has been classified as a dangerous detected DD failure Fail Low failure mode that caus...

Страница 7: ...shed via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms o...

Страница 8: ...esponding section as an example Connect 12 24 Vdc power supply positive at terminal 3 and negative at terminal 4 for channel 1 For Model D1014D connect 12 24 Vdc power supply positive at terminal 7 an...

Страница 9: ...allows the mA sink or source mode or Volt operating mode configuration Configuration Side A Panel View Span Trimmer CH1 Screwdriver for Trimmers 1 x 0 5 mm Dip switch configuration Vtx Adjust Ch1 Scr...

Страница 10: ...ly is the same for all channels there for don t separate the terminals because one channel remains switched off Different power supply Cut both pins of the connector to open the wiring between the ter...

Страница 11: ...llow step 1 Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA mA mA MODEL D1014D 14 15 3 4 1 2 10 11 5 6 7 8 V V Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA MODEL D1014D...

Отзывы: