D1014
- SIL 2 Repeater Power Supply Hart compatible
G.M. International ISM0052-16
3
Ordering information
Front Panel and Features
SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 9 / 10 years (
≤
10% / >10 % of total SIF).
PFDavg (1 year) 1.05 E-04, SFF 87.01%.
SIL 3 Systematic capability.
2 fully independent channels.
Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
4-20 mA Input, Output Signal.
Hart compatible.
Input and Output short circuit proof.
High Accuracy.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1
In-field programmability by DIP Switch.
ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
High Reliability, SMD components.
High Density, two channels per unit.
Simplified installation using standard DIN Rail and plug-in terminal blocks.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
Not used
Terminal block connections
HAZARDOUS AREA
SAFE AREA
+ Input Ch 2 for 2 wire Transmitters
- Input Ch 2 for 2 wire Transmitters
Not used
Not used
+ Input Ch 1 for 2 wire Transmitters
- Input Ch 1 for 2 wire Transmitters
Not used
9
10
11
12
13
14
15
16
+ Output Ch 1 for Current Source mode or + Output Ch 1 for
Voltage Source mode or + Output Ch 1 for Current Sink mode
1
- Output Ch 1 for Current Source mode or - Output Ch 1 for
Voltage Source mode or - Output Ch 1 for Current Sink mode
2
+ Ch 1 Power Supply 12-24 Vdc
3
- Ch 1 Power Supply 12-24 Vdc
4
+ Output Ch 2 for Current Source mode or + Output Ch 2 for
Voltage Source mode or + Output Ch 2 for Current Sink mode
5
- Output Ch 2 for Current Source mode or - Output Ch 2 for
Voltage Source mode or - Output Ch 2 for Current Sink mode
6
+ Ch 2 Power Supply 12-24 Vdc
7
- Ch 2 Power Supply 12-24 Vdc
8
Model:
D1014
1 channel
S
Power Bus enclosure
2 channels
D
/B
Power Bus and DIN-Rail accessories:
DIN rail anchor MCHP065
DIN rail stopper MOR016
Terminal block male MOR017
Terminal block female MOR022