Clarity 26 FS IPI
AIR SHUTTER ADJUSTMENT
The air shutter allows the amount of air coming
into the fi replace to be adjusted in order to
accommodate diff erent climates and venting
arrangements.
1. To access the air shutter adjustment lever,
open the hinged door beneath the fi rebox, it
is in the upper left-hand side. (
Fig.17
)
2. Start the pilot and then the burner. Allow
the appliance to operate for 15 minutes
before making any air adjustments.
3. The ideal fl ame will be blue at the base and
light orange above. If the fl ames are short
and mostly blue, the fi replace is getting too
much air. Therefore, the air shutter should
be closed slightly until the correct fl ames
are achieved. Slide the air shutter to the
right to reduce the amount of air.
4. Flames that are very orange, with tall,
dark, stringy tips, are not getting enough
air. Therefore, the air shutter should be
opened slightly until the correct fl ames are
achieved. Slide the air shutter to the left to
increase the amount of air.
5. Tighten air shutter lock screw.
BURNER FLAME APPEARANCE
The ideal fl ame will be blue at the base and
light orange above. If the fl ames are short and
mostly blue, the fi replace is getting too much
air. Therefore, the air shutter should be closed
slightly until the correct fl ames are achieved,
see air shutter adjustment above.
Flames that are very orange, with tall dark,
stringy tips, are not getting enough air.
Therefore, the air shutter should be opened
slightly until the correct fl ames are achieved,
see air shutter adjustment above.