The following symbols apply to multiple component types. Component-specific symbols are detailed below for
each component separately.
OFF
The entire system/boiler/power distribution or component is switched off.
None
Symbol
Ready
The component is in standby. When all start conditions are satisfied, it goes into active
mode.
Active
See description of component (below)
Warning
The component cannot operate properly. Messages (see page 21) are accompanied by
a corresponding entry.
Frost
protection
Components
Boiler with current boiler
temperature
Fill day container, prepare for ignition, ignition,
STL process
Burn, heat, burn out, post-ventilate
Buffer with upper and
lower temperature
Buffer charging in progress
i
Even though buffer loading is shown to be active, the charging pump is not necessarily running.
The buffer charging pump is only activated when the boiler temperature is at least 3° C greater than
the upper buffer temperature. When the boiler temperature is less than 1° C greater than the upper
buffer temperature, the charging pump is switched off.
Hot water with current
temperature
Hot water charging active (see buffer information above)
Heating circuit with current
flow temperature
Day operation (within the set time window) The flow
calculation is done in relation to the "Day temperature"
setting
Lowering mode (outside the set time window). The
flow calculation is done in relation to the "Reduced
temperature" setting
Summer mode. The heating circuit is switched off (pump
off, mixer closed)
Solar with current collector
temperature
Solar charging active (pump running)