Operation Manual BioSmart PV-WM v.029.1|03.2021|en
Page 14 of 24
BioSmart PV-WM Reader
Operation Manual
Figure 6
–
Space for cable on the mounting plate
To ensure protection against the ingress of dust and moisture, the reader must be connected with
one Ethernet cable, which will then be pulled into the reader case through a sealed gland. Due to the fact
that the Ethernet cable connector wo
n’t pass through the cable gland, the cable should be “crimped” after
pulling it through the sealed lead-in.
Check the absence of breaks, short circuits and mechanical damage in the cables.
6)
Fix the mounting plate by screwing self-tapping screws into the dowels or screwing the screws into
the corresponding holes on the protective cover for BioSmart PV-WM.
7)
Unscrew the screws on the back cover of the reader (see Figure 7), remove the back cover.
Figure 7
–
Rear cover attachment points
8)
Insert the Ethernet cable through the hole in the back cover of the reader, insert the connector into
the Ethernet port and secure the rear cover of the reader. To achieve the declared IP54 protection
degree, follow the steps below.
It’s
recommend to take the following measures to ensure protection against dust and moisture,
regardless of the intended operating conditions, as taking these steps increases the device survivability.
Measures to ensure protection of the reader from dust and moisture:
a)
install the sealed lead-in on the reader back cover. The sealed lead-in composition is shown in Figure
8.
Space for
cable
Rear cover
attachment
points