16
MPR180416 Rev. B
www.bindicator.com
QUICK START WIZARD PARAMETER SHEET
The following six parameters are needed to use the Quick Start Wizard; this page can be printed for easy set-up.
VESSEL (QUESTION 1)
Select vessel construction material:
•
STEEL
•
CONCRETE
RESPONSE RATE (QUESTION 2)
Sets the reaction speed of the device to measurement changes in the target range.
Response
Rate
Vessel Fill Rate/Min or Empty Rate/Min
SLOW
0.32 ft/min (0.1 m/min)
MED
3.28 ft/min (1.0 m/min)
FAST
32.8 ft/min (10.0 m/min)
Use a setting just faster than the maximum vessel filling or vessel emptying rate (whichever is greater)
MED response rate is set as the Default.
UNITS (QUESTION 3)
Sensor measurement units:
•
Meters (m) - DEFAULT
•
Centimeters (cm)
•
Millimeters (mm)
•
Feet (ft)
•
Inches (in)
OPERATION (QUESTION 4)
Operation
Description
LEVEL (1)
Distance from Low Calibration Point to material surface
SPACE (2)
Distance from High Calibration Point to material surface
DISTANCE (3)
Distance from Sensor Reference Point to material surface (flange face)
LOW CALIBRATION POINT (QUESTION 5)
Distance from Sensor Reference Point to Low Calibaration
Point: usually process empty level.
Value Range: 0.000 to 40.000 m or 0.000 to 100.000 m
(Default: 40.000 m or 100.000 m)
HIGH CALIBRATION POINT (QUESTION 6)
Distance from Sensor Reference Point to High Calibration
Point: usually process full level.
Value Range: 0.000 to 40.000 m or 0.000 to 100.000 m
(Default: 40.000 m or 100.000 m)
High Point minus Low Point must not be less than zero or error will occur.
LEVEL (1)
SPACE (2)
DISTANCE (3)
HIGH
CALIBRATION
POINT
LOW
CALIBRATION
POINT
Содержание F78MP Series
Страница 1: ...F78MP Series Air Radar Installation Operation Manual IOM MPR180416 Rev B...
Страница 2: ......
Страница 45: ...41 www bindicator com MPR180416 Rev B NOTES...
Страница 46: ...42 MPR180416 Rev B www bindicator com NOTES...
Страница 47: ...43 www bindicator com MPR180416 Rev B NOTES...