GERNERAL FAULT CODES

• 

If more than one fault is present, the device status indicator and text for each fault alternate at 2 second intervals.

• 

If you receive an LOE error communicated via the communications bus, double-check with the device LUI prior to 
contacting the service department. Occasionally the device will show a hardware fault (S96) that is reported through 
the bus as an LOE. In such a case, the device electronics will need to be replaced.

Code/Icon

Meaning

Corrective Action

S:0

The device was unable to get a measurement 
within the Fail-Safe LOE Timer period. 
Possible causes: faulty installation, antenna 
material buildup, foaming/other adverse 
process conditions, invalid calibration range.

• 

Ensure installation details are correct.

• 

Ensure no material buildup. Clean if necessary.

• 

Adjust process conditions to minimize foam or other 
adverse conditions.

• 

Correct range calibration.

• 

If fault persists, contact your local Bindicator 
representative.

S:2

Unable to collect profile because of a
power condition that is outside the 
operating range of the device.

• 

Repair required. Contact your local Bindicator 
representative.

S:3

Device is nearing its lifetime limit according 
to the value set in Maintenance Demanded 
Limit.

• 

Replacement is recommended.

S:4

Device is nearing its lifetime limit according 
to the value set in Maintenance Demanded 
Limit.

• 

Replacement is recommended.

S:6

Sensor is nearing its lifetime limit according 
to the value set in Maintenance Demanded 
Limit.

• 

Replacement is recommended.

S:7

Sensor is nearing its lifetime limit according 
to the value set in Maintenance Demanded 
Limit.

• 

Replacement is recommended.

S:8

Service interval as defined in Maintenance 
Required Limit has expired.

• 

Perform service.

S:9

Service interval as defined in Maintenance 
Required Limit has expired.

• 

Perform service.

S:11

Internal temperature sensor failure

• 

Repair required; contact Bindicator

S:12

Internal temperature of device has exceeded 
specifications: it is operating out-side its 
temperature range.

• 

Relocate device and/or lower process temperature 
enough to cool device. 

• 

Inspect for heat-related damage and contact 
Bindicator if repair is required.

• 

Fault code will persist until a manual reset is 
performed using SIMATIC PDM or the LCD interface.

Содержание F78MP Series

Страница 1: ...F78MP Series Air Radar Installation Operation Manual IOM MPR180416 Rev B...

Страница 2: ......

Страница 3: ...II GENERAL SAFETY 2 Authorized Personnel Use Misuse III PRODUCT DESCRIPTION 4 Function Technical Specifications IV MECHANICAL INSTALLATION 6 Guidelines Mounting Considerations V ELECTRICAL INSTALLATIO...

Страница 4: ...ES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS INJURY RISK OF ELECTRICAL SHOCK CAUTION IDENTIFIES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS DAMA...

Страница 5: ...ING This product can be recycled by specialized companies and must not be disposed of in a municipal collection site If you do not have the means to dispose of properly please contact for return and d...

Страница 6: ...If any questions or problems arise during installation of this equipment please contact Customer Support at 800 778 9242 INDUSTRY CANADA The MP Series radar complies with Industry Canada standard RSS...

Страница 7: ...xed locations Devices shall not operate while being moved or while inside a moving container Hand held applications and residential use are prohibited R TTE COMPLIANCE EUROPE Hereby Bindicator declare...

Страница 8: ...lds very good reflection properties on sloped solids so aiming towards material angle of repose is usually not necessary The technology is very tolerant to buildup on the lens antenna however an air p...

Страница 9: ...ine Length 4921 ft 1500 m multi wire Humidity 45 to 75 relative humidity Dielectric Constant Minimum dK of 1 6 for ranges up to 65 6 ft 20 m Minimum dk of 2 5 for ranges up to 328 ft 100 m PHYSICAL Ma...

Страница 10: ...DANCE WITH SOUND ENGINEERING PRACTICE SEP SEE EU COMMISSION GUIDELINE 1 5 GUIDELINES CONSIDERATIONS The following precautions should be observed when installing the MP Series air radar units Correct l...

Страница 11: ...flange see instructions below 1 For 4 and 6 Aimer Loosen the set screws in the locking ring Holding the electronics enclosure firmly loosen the Aimer locking ring using the supplied C spanner until t...

Страница 12: ...one of 4 positions 90 degrees apart It can also be used to transfer parameters from one device to another Can be removed with power applied Sun Shield Optional Accessory The MP Series air radar displa...

Страница 13: ...ended It is the customer s responsibility to ensure that any vacuum or pressure in the measured vessel is maintained considering the hole that passes through the process connection and MP Series anten...

Страница 14: ...that apply Properly ground the enclosure to an adequate earth ground Do not modify any factory wiring Connections should only be made to the terminals described in this section Do not allow moisture...

Страница 15: ...C RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED INCLUDING INTERFERENCE THAT MAY CA...

Страница 16: ...C or integral to it HART resistance total loop resistance that is cable resistance plus 250 Ohm resistor must be less than 550 Ohm for the device to function properly Power Supply PLC HART Modem HART...

Страница 17: ...ain see the Language Menu Measurement Mode Display Normal Operation 1 Toggle indicator for primary value PV or secondary value SV Press UP or DOWN arrow to switch 2 Selected operation level space or d...

Страница 18: ...riod of inactivitiy in Program Mode set via Timeout Menu For a complete list of parameters go to page XX Selecting an Option 1 Navigate to the desired parameter using the menu and LDI buttons 2 Press...

Страница 19: ...ght the next digit to the right 4 Use UP arrow or DOWN arrow to modify the highlighted digit Scroll past 9 to reach the decimal point 5 When the value is complete press RIGHT arrow until the ENTER ico...

Страница 20: ...s Meters m DEFAULT Centimeters cm Millimeters mm Feet ft Inches in OPERATION QUESTION 4 Operation Description LEVEL 1 Distance from Low Calibration Point to material surface SPACE 2 Distance from High...

Страница 21: ...in Therefore SLOW response rate 0 1 m min can be selected Quick Start Parameter Setting Description Vessel STEEL Selects vessel construction material Response Rate SLOW Resets Fill Rate Empty Rate to...

Страница 22: ...an area position the intersection of the cross hairs at the center of that area select Zoom and press RIGHT arrow Press LEFT arrow to Zoom out 6 To update the profile select Measure and press RIGHT ar...

Страница 23: ...nd press RIGHT arrow to transfer it 7 Press DOWN arrow to initiate learn A transition screen appears followed by the message Wizard Complete 8 Press DOWN arrow Finish to save AFES parameter changes an...

Страница 24: ...characters Read only on device Read only on device Read write using SIMATIC PDM and AMS 2 1 3 Descriptor Text that can be used in any way Limited to 16 ASCII characters No specific recommended use Rea...

Страница 25: ...to configure the device 2 3 1 Low Calibration Point Distance from sensor reference point to Low Calibration Point Units are definited in Units 2 2 1 and displayed on the LCD Value Range 0 to 100 00 m...

Страница 26: ...ft min 10 0 m min 2 4 3 Empty Rate Min Defines the maximum rate at which the reported sensor value is allowed to decrease Allows you to adjust the unit response to increases in the actual material lev...

Страница 27: ...100 and Current Output Function 2 6 1 determines whether this is a Level Space or Distance measurement Value Range 999999 to 999999 Defualt 40 00 or 100 0 m Enter the reading that is to correspond to...

Страница 28: ...cho Default AL Echo Area Largest AF Echo Area First LF Echo Largest First BLF Best of First and Largest Echo BL Best Largest Echo BF Best First Echo LAST TF True First Echo 2 4 3 2 Echo Threshold Sets...

Страница 29: ...alid reading based on numbers of samples above or below the currently selected echo 2 7 4 1 Echo Lock Selects the measurement verification process Lock Off Maximum Verification Not recommended for rad...

Страница 30: ...known obstructions A learned TVT time varying threshold replaces the default TVT over a specified range 2 8 2 Auto False Echo Suppression Range Defines the endpoint of the Learned TVT distance Units...

Страница 31: ...1 Min Measured Value The minimum recorded sensor value reported in units 3 4 2 Max Measured Value The maximum recorded sensor value reported in units 3 4 3 Minimum PV The minimum recorded Primary Val...

Страница 32: ...Expected 3 6 6 less Time in Operation 3 6 1 3 6 3 Reminder 1 Required If remaining lifetime 3 6 2 is equal or less than this value the device generates a Maintenance required reminder Value Range 0 to...

Страница 33: ...quired If remaining lifetime 3 7 2 is equal or less than this value the device generates a Maintenance required reminder Value Range 0 to 20 years Default 0 164 years 3 7 4 Reminder 2 Demanded If rema...

Страница 34: ...he factory setting is for optimum visibility at room temperature and in average light conditions Extremes of temperature will lesson the contrast Range 0 to 20 Default 8 Contrast setting will depend o...

Страница 35: ...fter performing a service Can be reset locally by entering 0 into this parameter 4 8 2 Time until Next Calibration Read only Calibration interval 4 8 6 less Time since Last Calibration 4 8 1 4 8 3 Rem...

Страница 36: ...to 15 for a HART 5 master Range 0 to 63 Default 0 5 2 Remote Lock Enables disables the read write access to parameters via remote communications ON No Changes are permitted via remote communications...

Страница 37: ...lution that will not react adversely with either Remove the instrument from service and wipe the antenna clean using a cloth and suitable cleaning solution UNIT REPAIR AND EXCLUDED LIABILITY All chang...

Страница 38: ...a warning limit 3 Process value has reached a tolerance limit 1 Configuration error Device will not work because one or more parameters components is incorrectly configured 2 Configuration warning Dev...

Страница 39: ...dition that is outside the operating range of the device Repair required Contact your local Bindicator representative S 3 Device is nearing its lifetime limit according to the value set in Maintenance...

Страница 40: ...i bration Point and Low Calibration Point is not less than or equal to zero do a Master Reset S 52 Fail Safe is activated Possible causes 1 hardware failure 2 memory failure 3 Fail safe LOE timer expi...

Страница 41: ...eck nozzle for internal burrs or welds use Auto False Echo Suppression 2 4 8 1 if necessary see Auto False Echo Suppression 2 4 8 1 Measurement is consistently off by a constant amount setting for Low...

Страница 42: ...vel material is within Near Range zone multiple echoes processed decrease Near Range 2 4 1 minimum value depends on model raise unit ensure Algorithm 2 4 5 1 is set to tF trueFirst echo vessel near em...

Страница 43: ...E 2 6 8 MA OUTPUT VALUE 2 7 SIGNAL PROCESSING 2 7 1 NEAR RANGE 2 7 2 FAR RANGE 2 7 3 ECHO SELECT 2 7 3 1 ALGORITHM 2 7 3 2 ECHO THRESHOLD 2 7 3 3 POSITION DETECT 2 7 3 4 CLEF RANGE 2 7 3 5 ECHO MARKER...

Страница 44: ...ETIME EXPTECTED 3 7 7 MAINT STAT 3 7 8 ACK STATUS 3 7 9 ACK 4 SERVICE 4 1 DEMO MODE 4 2 MASTER RESET 4 3 POWERED HOURS 4 4 POWERON RESETS 4 5 LCD BACKLIGHT 4 6 LCD CONTRAST 4 7 SERVICE SCHEDULE 4 7 1...

Страница 45: ...41 www bindicator com MPR180416 Rev B NOTES...

Страница 46: ...42 MPR180416 Rev B www bindicator com NOTES...

Страница 47: ...43 www bindicator com MPR180416 Rev B NOTES...

Страница 48: ...150 Venture Boulevard Spartanburg SC 29306 Tel 800 778 9242 Fax 864 574 8063 sales bindicator com www bindicator com 2016 All rights reserved All data subject to change without notice MPR180416 Rev B...

Отзывы: