AIR PURGE

All MP Series air radar models come standard with an air purge inlet. For convenient cleaning, a purging inlet is provided 

above the antenna. The system provides an 1/8” inlet (female thread) above the antenna where clean, dry air passes to 

the face of the antenna lens to clean it. The customer will supply the purging air by a manual or automatic valve system.

• 

Purge duration, pressure, and interval, will vary with each application. It is the user’s responsibility to determine the 

requirements depending on the application and cleaning required.

• 

Short duration bursts of high pressure provide more effective cleaning than continuous low pressure air.

• 

Some dust particles are highly abrasive and can cause wear on the lens face over time if continuous air purge is used, 

therefore short bursts are recommended.

• 

It is the customer’s responsibility to ensure that any vacuum or pressure in the measured vessel is maintained, 
considering the hole that passes through the process connection and MP Series antenna system.

Acceptable Air Consumption 

(Flow rate vs applied pressure)

Air Pressure (psi)

Approx. inlet volume
 flow rate (SCFM)

20

5

40

10

50

15

80

20

100

25

110

30

Recommended 90 to 110 psi for effective cleaning

PURGE CONNECTION

• 

The purge connection is closed by the manufacturer, using a 1/8” plug (standard on all units).

• 

When the plug is removed to connect a purging system, the operator is responsible for ensuring that the purging 

circuit conforms to explosion protection requirements: for example, by fitting an NRV valve. Air pressure in vessel can 

affect purge operation.

PURGE AIRFLOW

• 

The purge airflow is designed to create a strong vortex of air that rapidly cleans the face of the lens.

• 

The air purge system can clean both dust and moisture off the lens.

Angled holes direct air flow

Purge process connection with 

factory installed 1/8” NPT plug

Содержание F78MP Series

Страница 1: ...F78MP Series Air Radar Installation Operation Manual IOM MPR180416 Rev B...

Страница 2: ......

Страница 3: ...II GENERAL SAFETY 2 Authorized Personnel Use Misuse III PRODUCT DESCRIPTION 4 Function Technical Specifications IV MECHANICAL INSTALLATION 6 Guidelines Mounting Considerations V ELECTRICAL INSTALLATIO...

Страница 4: ...ES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS INJURY RISK OF ELECTRICAL SHOCK CAUTION IDENTIFIES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS DAMA...

Страница 5: ...ING This product can be recycled by specialized companies and must not be disposed of in a municipal collection site If you do not have the means to dispose of properly please contact for return and d...

Страница 6: ...If any questions or problems arise during installation of this equipment please contact Customer Support at 800 778 9242 INDUSTRY CANADA The MP Series radar complies with Industry Canada standard RSS...

Страница 7: ...xed locations Devices shall not operate while being moved or while inside a moving container Hand held applications and residential use are prohibited R TTE COMPLIANCE EUROPE Hereby Bindicator declare...

Страница 8: ...lds very good reflection properties on sloped solids so aiming towards material angle of repose is usually not necessary The technology is very tolerant to buildup on the lens antenna however an air p...

Страница 9: ...ine Length 4921 ft 1500 m multi wire Humidity 45 to 75 relative humidity Dielectric Constant Minimum dK of 1 6 for ranges up to 65 6 ft 20 m Minimum dk of 2 5 for ranges up to 328 ft 100 m PHYSICAL Ma...

Страница 10: ...DANCE WITH SOUND ENGINEERING PRACTICE SEP SEE EU COMMISSION GUIDELINE 1 5 GUIDELINES CONSIDERATIONS The following precautions should be observed when installing the MP Series air radar units Correct l...

Страница 11: ...flange see instructions below 1 For 4 and 6 Aimer Loosen the set screws in the locking ring Holding the electronics enclosure firmly loosen the Aimer locking ring using the supplied C spanner until t...

Страница 12: ...one of 4 positions 90 degrees apart It can also be used to transfer parameters from one device to another Can be removed with power applied Sun Shield Optional Accessory The MP Series air radar displa...

Страница 13: ...ended It is the customer s responsibility to ensure that any vacuum or pressure in the measured vessel is maintained considering the hole that passes through the process connection and MP Series anten...

Страница 14: ...that apply Properly ground the enclosure to an adequate earth ground Do not modify any factory wiring Connections should only be made to the terminals described in this section Do not allow moisture...

Страница 15: ...C RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED INCLUDING INTERFERENCE THAT MAY CA...

Страница 16: ...C or integral to it HART resistance total loop resistance that is cable resistance plus 250 Ohm resistor must be less than 550 Ohm for the device to function properly Power Supply PLC HART Modem HART...

Страница 17: ...ain see the Language Menu Measurement Mode Display Normal Operation 1 Toggle indicator for primary value PV or secondary value SV Press UP or DOWN arrow to switch 2 Selected operation level space or d...

Страница 18: ...riod of inactivitiy in Program Mode set via Timeout Menu For a complete list of parameters go to page XX Selecting an Option 1 Navigate to the desired parameter using the menu and LDI buttons 2 Press...

Страница 19: ...ght the next digit to the right 4 Use UP arrow or DOWN arrow to modify the highlighted digit Scroll past 9 to reach the decimal point 5 When the value is complete press RIGHT arrow until the ENTER ico...

Страница 20: ...s Meters m DEFAULT Centimeters cm Millimeters mm Feet ft Inches in OPERATION QUESTION 4 Operation Description LEVEL 1 Distance from Low Calibration Point to material surface SPACE 2 Distance from High...

Страница 21: ...in Therefore SLOW response rate 0 1 m min can be selected Quick Start Parameter Setting Description Vessel STEEL Selects vessel construction material Response Rate SLOW Resets Fill Rate Empty Rate to...

Страница 22: ...an area position the intersection of the cross hairs at the center of that area select Zoom and press RIGHT arrow Press LEFT arrow to Zoom out 6 To update the profile select Measure and press RIGHT ar...

Страница 23: ...nd press RIGHT arrow to transfer it 7 Press DOWN arrow to initiate learn A transition screen appears followed by the message Wizard Complete 8 Press DOWN arrow Finish to save AFES parameter changes an...

Страница 24: ...characters Read only on device Read only on device Read write using SIMATIC PDM and AMS 2 1 3 Descriptor Text that can be used in any way Limited to 16 ASCII characters No specific recommended use Rea...

Страница 25: ...to configure the device 2 3 1 Low Calibration Point Distance from sensor reference point to Low Calibration Point Units are definited in Units 2 2 1 and displayed on the LCD Value Range 0 to 100 00 m...

Страница 26: ...ft min 10 0 m min 2 4 3 Empty Rate Min Defines the maximum rate at which the reported sensor value is allowed to decrease Allows you to adjust the unit response to increases in the actual material lev...

Страница 27: ...100 and Current Output Function 2 6 1 determines whether this is a Level Space or Distance measurement Value Range 999999 to 999999 Defualt 40 00 or 100 0 m Enter the reading that is to correspond to...

Страница 28: ...cho Default AL Echo Area Largest AF Echo Area First LF Echo Largest First BLF Best of First and Largest Echo BL Best Largest Echo BF Best First Echo LAST TF True First Echo 2 4 3 2 Echo Threshold Sets...

Страница 29: ...alid reading based on numbers of samples above or below the currently selected echo 2 7 4 1 Echo Lock Selects the measurement verification process Lock Off Maximum Verification Not recommended for rad...

Страница 30: ...known obstructions A learned TVT time varying threshold replaces the default TVT over a specified range 2 8 2 Auto False Echo Suppression Range Defines the endpoint of the Learned TVT distance Units...

Страница 31: ...1 Min Measured Value The minimum recorded sensor value reported in units 3 4 2 Max Measured Value The maximum recorded sensor value reported in units 3 4 3 Minimum PV The minimum recorded Primary Val...

Страница 32: ...Expected 3 6 6 less Time in Operation 3 6 1 3 6 3 Reminder 1 Required If remaining lifetime 3 6 2 is equal or less than this value the device generates a Maintenance required reminder Value Range 0 to...

Страница 33: ...quired If remaining lifetime 3 7 2 is equal or less than this value the device generates a Maintenance required reminder Value Range 0 to 20 years Default 0 164 years 3 7 4 Reminder 2 Demanded If rema...

Страница 34: ...he factory setting is for optimum visibility at room temperature and in average light conditions Extremes of temperature will lesson the contrast Range 0 to 20 Default 8 Contrast setting will depend o...

Страница 35: ...fter performing a service Can be reset locally by entering 0 into this parameter 4 8 2 Time until Next Calibration Read only Calibration interval 4 8 6 less Time since Last Calibration 4 8 1 4 8 3 Rem...

Страница 36: ...to 15 for a HART 5 master Range 0 to 63 Default 0 5 2 Remote Lock Enables disables the read write access to parameters via remote communications ON No Changes are permitted via remote communications...

Страница 37: ...lution that will not react adversely with either Remove the instrument from service and wipe the antenna clean using a cloth and suitable cleaning solution UNIT REPAIR AND EXCLUDED LIABILITY All chang...

Страница 38: ...a warning limit 3 Process value has reached a tolerance limit 1 Configuration error Device will not work because one or more parameters components is incorrectly configured 2 Configuration warning Dev...

Страница 39: ...dition that is outside the operating range of the device Repair required Contact your local Bindicator representative S 3 Device is nearing its lifetime limit according to the value set in Maintenance...

Страница 40: ...i bration Point and Low Calibration Point is not less than or equal to zero do a Master Reset S 52 Fail Safe is activated Possible causes 1 hardware failure 2 memory failure 3 Fail safe LOE timer expi...

Страница 41: ...eck nozzle for internal burrs or welds use Auto False Echo Suppression 2 4 8 1 if necessary see Auto False Echo Suppression 2 4 8 1 Measurement is consistently off by a constant amount setting for Low...

Страница 42: ...vel material is within Near Range zone multiple echoes processed decrease Near Range 2 4 1 minimum value depends on model raise unit ensure Algorithm 2 4 5 1 is set to tF trueFirst echo vessel near em...

Страница 43: ...E 2 6 8 MA OUTPUT VALUE 2 7 SIGNAL PROCESSING 2 7 1 NEAR RANGE 2 7 2 FAR RANGE 2 7 3 ECHO SELECT 2 7 3 1 ALGORITHM 2 7 3 2 ECHO THRESHOLD 2 7 3 3 POSITION DETECT 2 7 3 4 CLEF RANGE 2 7 3 5 ECHO MARKER...

Страница 44: ...ETIME EXPTECTED 3 7 7 MAINT STAT 3 7 8 ACK STATUS 3 7 9 ACK 4 SERVICE 4 1 DEMO MODE 4 2 MASTER RESET 4 3 POWERED HOURS 4 4 POWERON RESETS 4 5 LCD BACKLIGHT 4 6 LCD CONTRAST 4 7 SERVICE SCHEDULE 4 7 1...

Страница 45: ...41 www bindicator com MPR180416 Rev B NOTES...

Страница 46: ...42 MPR180416 Rev B www bindicator com NOTES...

Страница 47: ...43 www bindicator com MPR180416 Rev B NOTES...

Страница 48: ...150 Venture Boulevard Spartanburg SC 29306 Tel 800 778 9242 Fax 864 574 8063 sales bindicator com www bindicator com 2016 All rights reserved All data subject to change without notice MPR180416 Rev B...

Отзывы: