22
MPR180416 Rev. B
www.bindicator.com
2.4 Rate
2.4.1 Reponse Rate: Sets the reaction speed of the device to measurement changes.
Response
Rate
Vessel Fill Rate/Min or Empty Rate/Min
Damping Filter
SLOW
0.32 ft/min (0.1 m/min)
10 s
MED
3.28 ft/min (1.0 m/min)
10 s
FAST
32.8 ft/min (10.0 m/min)
0 s
Use a setting just faster than the maximum filling/emptying rate (whichever is faster).
2.4.2 Fill Rate/Min: Defines the maximum rate at which the reported sensor value is allowed to increase. Allows you
to adjust the unit response to increases in the actual material level. Fill Rate is automatically updated whenever
Response Rate is altered.
Response Rate
Fill Rate
SLOW
0.32 ft/min (0.1 m/min)
MED
3.28 ft/min (1.0 m/min)
FAST
32.8 ft/min (10.0 m/min)
2.4.3 Empty Rate/Min: Defines the maximum rate at which the reported sensor value is allowed to decrease. Allows
you to adjust the unit response to increases in the actual material level. Fill Rate is automatically updated ..
whenever Response Rate is altered.
Response Rate
Empty Rate
SLOW
0.32 ft/min (0.1 m/min)
MED
3.28 ft/min (1.0 m/min)
FAST
32.8 ft/min (10.0 m/min)
2.5 Fail-Safe
2.5.1 Material Level: Defines the mA output to use when the Fail-Safe Timer expires
HI
20.5 mA (max mA limit)
LO
3.8 mA (min mA limit)
HOLD
Last valid reading; Default; 22.6 mA
VALUE
User selected value (Define in Level 2.5.3); Default 3.58 mA
2.5.2 Timer: Sets the time to elapse since the last valid reading, before the Fail-Safe Level is reported
Value Range: 0.00 to 720 s; Default 100 s
2.5.3 Level: Allows the user to define the mA value to be reported when the Fail-Safe timer expires.
Value Range: 3.56 mA to 22.6 mA; Default 3.56 mA