Installation, Operation and Maintenance Manual
VCIOM-08500-EN
Appendix
Appendix
B.6.2
Checks to be Performed Before Installation
Before installing extensions for additional entries or additional electronic cards on a base
ICON3000 unit, the following checks are recommended:
•
Condition of joint surfaces between compartment covers and the main housing.
•
Condition of the threads on the conduit entries.
•
Whether the enclosure covers or the actuator body are cracked or broken.
B.7 Installation
NOTICE
Installation must be carried out in accordance to the applicable standards IEC/EN 60079-14
and IEC/EN 60079-17 regarding the electrical installations in Hazardous Areas (other than
mines) classified as Zones 1, 2 (gas) and Zones 21, 22 (dust) following IEC/EN 60079-10-1
and IEC/EN 60079-10-2 and any other applicable national standards and rules.
B.7.1
Working Condition
WARNING
Verify that the actuator nameplate conforms to the applicable certification, ambient
temperature range, and site safety requirements.
B.7.1.1
Models and Temperature
ICON-010 and ICON-020
from - 60°C to +65°C (from -76°F to +149°F)
from - 60°C to +85°C (from -76°F to +185°F)
ICON-030, ICON-040 and ICON-050
from - 55°C to +65°C (from -67°F to +149°F)
from - 55°C to +85°C (from -67°F to +185°F)