The cables and cable glands MUST be selected considering the maximum temperature of
the cable indicated on the label fixed to the base ICON3000 unit. When selecting cables and
cable glands, the maximum temperature of the cable (indicated on the product label of the
base ICON3000) must be considered.
Figure A-3
A.7.5
Installation in Environments with Explosive Dusts
Special attention must be paid to the following points:
•
Before assembly, joint surfaces must be greased with Aeroshell grease.
•
The cable glands must at a minimum possess a protection degree of IP66 or IP68
(15 m depth / 90 hours) according to IEC/EN 60529 standard.
•
Periodically measure the quantity of dust deposited on the surface of the
actuator body. Clean the dust if it accumulates to more than 5mm high
(relative to the actuator body).
A.8 Maintenance
WARNING
Before performing service or maintenance operations (unless otherwise indicated),
ensure that power is turned off to the unit to avoid injury and/or damage to equipment.
WARNING
Installation, configuration, commissioning, maintenance, and repairs must be performed
by approved and qualified personnel only.
Internal earth stud
External earth stud
Connection for Ex-e
terminals enclosure