December 2019
71
Installation, Operation and Maintenance Manual
VCIOM-08500-EN
Section 9: Set-Up Routines
Set-Up Routines
9.3.1
Set Password
The actuator is supplied by Emerson with the default password (“0 0 0 0”).
The Set Password routine allows the user to enter a different password consisting of 4
alphanumeric characters. After entering the new password, the old one becomes invalid.
Therefore, it is mandatory to NOT FORGET THE PASSWORD (or store the password in a
secure location) after the default one has been modified. Losing the new password makes
it impossible to enter the set-up menu and to configure the actuator.
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press NO to scroll through the list of available menus and then
press YES to select the "Maintenance" menu.
•
Press NO to scroll the list of available routines and then press YES to select
"Set Password". Press YES again to select "Enter New Password".
•
Enter the new password one digit at a time. Press YES if the digit is correct;
otherwise, press NO to scroll through the list of available characters and
then press YES to select. Enter 4 digits. When the display shows the message
"Password Changed", the old password is no longer valid.
9.3.2
Clear Alarm Log
Clear procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press NO to scroll the list of available menus and then press YES
to select the "Maintenance" menu.
•
Press NO to scroll through the list of available routines and then press YES to
select "Clear Alarm Log".
•
Press YES to clear the alarm log.
9.3.3
Set Torque Reference
The set torque profile reference routine allows transfer of the last torque profile to the
reference profile registers. The old reference data are lost and the new data are used as a
new reference torque profile.
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press NO to scroll through the list of available menus and then
press YES to select the "Maintenance" menu.
•
Press NO to scroll through the list of available routines and then press YES to
select "Set Torque Reference".
•
Press YES to update the torque reference data.