33
5.1 PASSWORD
The current programming logic requires, when entering by pressing
the PROG key, the insertion of a password allowing to access one
programming menu.
To facilitate and speed up some operations on the fi eld, the pas-
sword management is subdivided as follows:
PWD 1 - Reduced programming menu
PWD 2 – Complete programming menu
PWD 3 – Sales Menu;
PWD 4 – Subdivided into 2 PWD set: 88000 to test all BVM600
slaves;
Test (managed by Bianchi Vending Group only) to access the test
carried out in the assembly line.
Note: If the password of the reduced menu coincides with the
password of the complete menu, the latter will prevail.
5.2 MACHINE and WINBIANCHI MENUS
PWD 1 allows the access the complete menu of the vending ma-
chine. The menu access procedure is as follows: press PROG key
on the master board, enter the password and press ENTER key.
Below is a list of WinBianchi menus and programming menus of
the vending machine.
5.2.1 WINBIANCHI MENUS
5.2.1.1 CONFIGURATION
This menu, available with WinBianchi Level 3 only, allows to as-
semble your vending machine as you like. The management of
the parts to be assembled will be of two types: graphic (through
the drawings of the mechanical parts) or question/answer (as the
current WB).
Below is a description of the Question/Answer structure.
Machine type
Selects the type of machine [BVM970, BVM
950, BVM 921, BVM600, BVM470]
Manag.Cold X
Selects the type of management of the
cold compressor [0/Snack/Pan/Can] Menu
available only with machine type BVM600/
BVM470].
1: None
Cold management not enabled
2 : Snack confi guration
Settings/values:
Tank temperature
Delta
temperature
Offset
Ex.
: if we set tank temper. =6°, delta temper. = 2° and offset
=0 when we read the value 6 on the display, the temperature of
the bottom cabinet will be = 6° and the compressor will stop to
restart at 8°.
if we set tank temper. = 6°, delta temper. = 2° and offset = -
3 when we read the value 6 on the display, the temper. of the
bottom cabinet will in fact be 9° (i.e.the display will show a value
3° lower than the temper.of the bottom cabinet). The compressor
will stop with temper. of the bottom cabinet at 9° ( but the display
will continue showing 6°) to restart at 11° ( but the display will
continue showing 8°) if we set the tank temper. = 6°, delta temp.
= 2° and offset =+3 when we read the value 6 on the display, the
temper. of the bottom cabinet will in fact be 3° (i.e.the display will
show a value 3° higher than the temper.of the bottom cabinet).
The compressor will stop with temper. of the bottom cabinet at
3° to restart at 5°.
Defrost after x hours: provides the sequence of the defrosting
intervention. i.e. the time interval after which the compressor will
stop to let the evaporator defrost.
Defrost after x minutes: is the period of time during which the
compressor is at stop.
In this case the impeller inside the tank will continue rotating.