20
1. Press
the
UP ARROW
and
ENTER
keys to enter the
Secondary Menu.
2. Press
the
INDEX
key until
Fint
appears on the display.
Fint
determines the amount of impact fuzzy logic will have on the
output, and can be 0 to 100%. 0% is OFF.
3. Use
the
UP ARROW
and
DOWN ARROW
keys to change the
value.
4. After a value is selected, press
ENTER
to retain that value.
The following menu items will not appear if
Fint
is set to 0%.
5. Press
the
INDEX
key until
Fbnd
appears on the display.
Fbnd
is the bandwidth of the fuzzy logic, and can be set at 0 to 4000.
The units depend on what value the menu item
Unit
is set for.
Set
Fbnd
equal to PID proportional band for best results.
6. Use
the
UP ARROW
and
DOWN ARROW
keys to change the
value.
7. After a value is selected, press
ENTER
to retain that value.
8. Press
the
INDEX
key until
FrtE
appears on the display.
FrtE
is
the fuzzy logic’s rate of change with a range of 0.00 to 99.99
counts/second. For best initial setting, find the count/second
change of process value near setpoint 1 with output on.
Multiply this value by 3 and set FrtE to this value.
9. Use
the
UP ARROW
and
DOWN ARROW
keys to change the
value.
10. After a value is selected, press
ENTER
to retain that value.
Installation
The following procedure should be used when installing the
BriskONE temperature controller.
1. Choose an appropriate location with the following:
•
Proximity to a suitable power supply.
•
Appropriate clearances (for example: clearance to allow
easy installation of connectors).
•
Ambient temperature does not go beyond the range of -
10 to +55
o
C (+14 to 131
o
F).
•
Humidity conditions do not go beyond 0 to 90% up to 40
o
C non-condensing, 10 to 50% at 55
o
C non-condensing
2. If the temperature controller is not to be mounted, then:
•
The controller’s resting surface must be stable and easy
to access for inspection.