1
3
4
. Press
ENTER
to retain that value.
If
OFF
is selected for the value for
AL
, the following menu
items will not appear.
5. Press
the
INDEX
key until
ALT
appears on the display.
ALT
is
the menu item that selects the temperature alarm type. There are
two values to choose from.
•
AbS
Absolute Alarm may be set anywhere between 0-
1600 and is independent from
SP1
.
•
dE
Deviation Alarm is dependent on
SP1
, and alarms
when the process temperature is beyond acceptable
limits enter in
ALLo
and
ALHi
.
6
. Use the
UP ARROW
and
DOWN ARROW
keys to change the
value.
7
. After a value is selected, press
ENTER
to r etain that value.
8.
Press the
INDEX
key until
ALiH
is shown on the lower display.
ALiH
is the alarm inhibit menu item.
•
On
The alarm action is suspended until the process
temperature first enters a non-alarm condition.
•
OFF
Turns the alarm inhibit off.
9
. Use the
UP ARROW
an
d
DOWN ARROW
keys to change the
value.
10
.
After a value is selected, press
ENTER
to retain that value.
11
.
Press the
INDEX
key
until
ALS
t
appears on the display.
ALSt
is the alarm output state menu item. BriskONE’s design
requires
ALSt
be set to
OPEn
.
If
ALSt
is set to
CLOS
, then press
UP ARROW
and
DOWN
ARROW
keys until the value shown is
OPEn
. Press
ENTER
to retain that value
12
.
Press th
e
INDEX
key until
ALLP
appears on the display.
ALLP
is the alarm lamp. BriskONE’s design requires
ALLP
be
set to
OoFF
.
If
ALLP
is set to
O on
, the press
UP ARROW
and
DOWN
ARROW
keys until the value shown is
OoFF
. Press
ENTER
to retain that value.