FENIX2 Monitoring system – Commissioning instruction

For local 0-10 V  
control from, for  
example room  
sensors, the  
FENIX 0-10 V  
module is used.

Connection terminals Function

Description

4+5, 11+12

Connection of smoke detector 
circuits

Each smoke detector circuit should have a 2.2 kOhm's resistance mounted at the 
end of the circuit, see the wiring diagram. The terminating resistance of 2.2 kOhm is 
connected to the last detector in each circuit. If a central fire alarm and/or no smoke 
detectors are used, a resistance of 2.2 kOhm should not be installed on these terminals. 
Max 24 V DC 90 mA.

6-10, 13-17

Connection of fire damper

For standard ON/OFF dampers, the input is not used for 10 V, this is done only for regu-
lating dampers, see wiring diagrams. 
The damper output on G and G0 is 24 V DC, max 10 VA per output.

Note! Only 1 fire damper per output!

Inputs

Function

Description

32+33

External function test/resetting 
External alarm

In the event of a short circuit, the controller performs a functional test and may reset the 
external incoming alarm, provided that terminals 34+35 do not have an open circuit. 
These terminals cannot be jumpered for automatic resetting. Instead, see options under 
settings.

34+35

External incoming alarm

In the event of an open circuit between terminals, External incoming alarm is activated, 
jumpered on delivery and if External incoming alarm is not used.

36+37

Night mode

In the event of short circuiting of the terminals, the panel enters Night mode whereby 
all dampers close without the controller generating alarms. Used, for example, during 
intermittent operation. Night mode can also be a good safety measure for preventing the 
spread of combustion gases when the ventilation is switched off, duct-mounted smoke 
detectors do not have the same opportunity to detect smoke when no air is transported 
in the system. 

Outputs

Function

Description

38+39+40

Main alarm

Potential-free changeover contact that switches for: 
• Detector failure • Damper failure • Tripped detector • External incoming alarm  
• Power outage • System failure • Communication failure with slave units  
• Internal battery needs to be replaced 
In normal operation, terminals 38+40 have contact. 
Drawn in de-energised/alarm mode. 
Max 24 V AC/DC, 3 A

41+42+43

Service alarm detector circuits

Potential-free changeover contact that switches for soiled detector. 
In normal operation, terminals 41+43 have contact.
Drawn in de-energised/alarm mode. 
Max 24 V AC/DC, 3 A

44+45

External stop of fan/unit

Breaking potential-free contact that breaks for: 
• Functional testing of fire dampers • Main alarm 
In normal operation, terminals 44+45 have contact. 
Drawn in de-energised/alarm mode. 
Max 24 V AC/DC, 3 A

Network connection

Cable connection RJ45, 10Base-T/100Base-TX auto-negotiation
Cable length Max. 100 m
Cabling Min. Cat 5

2. Connection cont.

•  Measure the voltage with a 

multimeter use a well-known 
brand.

•  Check cables using an 

Ohmmeter with all devices 
disconnected.

•  Never use a megohmmeter!

•  All cable connections and 

disconnections are done with 
the FENIX2 powered down.

Содержание Fenix 2

Страница 1: ...21 01 2021 FENIX2 Monitoring system Commissioning instruction FIRE SAFETY www bevent rasch com...

Страница 2: ...contains electronic components that can be damaged if used incorrectly When connecting dampers smoke detectors and other con nections the unit must be powered down The cover to access the terminal bl...

Страница 3: ...Modbus TCP or BACnet IP If local control is desired with 0 10 V the FENIX 0 10 V module is used to separate the local control signal from e g a room sensor and the 10 V signal from FENIX2 that takes o...

Страница 4: ...ector RCRD DAMPER DAMPER 3 DAMPER DAMPER 4 18 20 21 22 23 24 DET3 19 S2 S6 G0 G 0 10 V 25 27 28 29 30 31 DET4 N N A A B B 26 S2 S6 G0 G 46 47 48 0 10 V Connections in RCHD Connections in RCHD Connecti...

Страница 5: ...ting of the terminals the panel enters Night mode whereby all dampers close without the controller generating alarms Used for example during intermittent operation Night mode can also be a good safety...

Страница 6: ...arted Use the troubleshooting guide on the display to correct the fault before commissioning Check that the number of fire dampers and smoke detector circuits found match the installation Use the trou...

Страница 7: ...box On Off Damper in middle position Open damper DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLA...

Страница 8: ...r a 5 minute delay which then allows the electric heating coils to cool down Default setting no delay Automatic reset of External incoming alarm Normally an External incoming alarm 34 35 needs to be a...

Страница 9: ...to be replaced This can also be done in connection with service or an obligatory ventilation control OVK Instructions for replacing the battery 1 Power down the unit no 230 V AC must be connected whe...

Страница 10: ...10 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 11: ...11 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 12: ...191203 0001_ENG January 2021 teamfront se www bevent rasch com...

Отзывы: