FENIX2 Monitoring system – Commissioning instruction

2. Connection

Connect dampers, smoke detectors and other connections according to the 
following connection instructions when the unit is powered down.  

NOTE! If a smoke detector is not connected, then no

terminating resistance 

should 

 be fitted.

The connection instructions for the ON/OFF damper (open/closed) are different 
from the regulating 0-10 V damper, see the connection instructions.

4

6 7 8 9 10

DET1

5

32

FUNC.

TEST

33 34

EXT.

ALARM

35 36

NIGHT

MODE

37

S2

S6

G0

G

0-10 

V

11

13 14 15 16 17

DET2

12

S2

S6

G0

G

0-10 

V

INPUTS

38

SUM.

ALARM

DET. SERV.

ALARM

39 40 41 42

44 45

EXT.

STOP

43

OUTPUTS

C

NC

NO

C

C

NC

NO

NO

X

ON/OFF damper

X

2

6 4 1

5

1 2

3

5

X

3

5

2

1

1

4

6

2

3

FENIX 0-10 V

0-10 V damper

Example 0-10 V damper 

with local control signal 

0-10 V and FENIX 0-10 V 

module

Example common 

ON/OFF damper

X

X

DAMPER/

DAMPER 1

DAMPER/

DAMPER 2

1

2

3

230 VAC 
100 VA 
50 Hz

X

X

0-10 V damper *)

X

2

6 4 1

5

5

1 2

3

3

Example 0-10 V damper with 

control via Modbus/BACnet

Connections 
in RCHD

Connections 
in RCHD

1 2

1 2

3
6

1

***) For 

channel

detector

 RCKD

**) At room 

detector RCRD

4

6 7 8 9 10

DET1

DAMPER/

DAMPER 3

DAMPER/

DAMPER 4

5

S2

S6

G0

G

0-10 

V

11

13 14 15 16 17

DET2

12

S2

S6

G0

G

0-10 

V

18

20 21 22 23 24

DET3

19

S2

S6

G0

G

0-10 

V

25

27 28 29 30 31

DET4

N

N

A

A

B

B

26

S2

S6

G0

G

46 47 48

0-10 

V

X

ON/OFF damper *)

X

2

6 4 1

5

1 2

3

5

X

3

5

2

1

1

4

6

2

3

FENIX 0-10 V

0-10 V damper *)

Example 0-10 V

Example ON/OFF

Connections 
in RCHD

Connections 
in RCHD

Connections in 
RCHD

Connections in 
RCKD

X

X

DAMPER/

DAMPER 1

DAMPER/

DAMPER 2

1

2

3

SLAVE ADDRESS

3

1

2

230 VAC 100 VA 50 Hz

1 2

Overtemperature detector RCHD 
together with smoke detector

1 2

1

2

1 2 3 4 5

FENIX+ 
slave unit

FENIX+ slave unit 

or FENIX4

COM

FENIX2

Cable recommendations

ON/OFF dampers, e.g. BSKC6 = EKKR/ELQRB/EQQRB 4x1 mm

2

Regulating damper 0-10 V, e.g. BSKC6R = EKKR/ELQRB/EQQRB 5x1 mm

2

  

(7x1 mm

2

)

For local 0-10 V  
control from, for  
example room  
sensors, the  
FENIX 0-10 V  
module is used.

S2 S6 G0 G

X

X

FENIX2

0-10 V

S2 S6 G0

G0

G

0-10 V 0-10 V

S6

S2

S4

1

-

S1

0-10 V

2

+

FENIX 0-10 V

3 5

X

External 0-10 V signal 
from room sensors, 
for example

0-10 V damper *)

***) For duct detector RCKD 

connected in series

**) For room detector RCRD 

connected in series

*) 24 V DC max. 10 VA 

When separate thermal 
sensor is used, connect 
in series with motor.

3

6

1

3

6

1

Actuator

***) For duct detector RCKD 

connected in series

**) For room detector RCRD 

connected in series

*) 24 V DC max. 10 VA 

When separate thermal 
sensor is used, connect 
in series with motor.

3

6

1

3

6

1

Actuator

***) For duct detector RCKD 

connected in series

**) For room detector RCRD 

connected in series

*) 24 V DC max. 10 VA 

When separate thermal 
sensor is used, connect 
in series with motor.

3

6

1

3

6

1

Actuator

Содержание Fenix 2

Страница 1: ...21 01 2021 FENIX2 Monitoring system Commissioning instruction FIRE SAFETY www bevent rasch com...

Страница 2: ...contains electronic components that can be damaged if used incorrectly When connecting dampers smoke detectors and other con nections the unit must be powered down The cover to access the terminal bl...

Страница 3: ...Modbus TCP or BACnet IP If local control is desired with 0 10 V the FENIX 0 10 V module is used to separate the local control signal from e g a room sensor and the 10 V signal from FENIX2 that takes o...

Страница 4: ...ector RCRD DAMPER DAMPER 3 DAMPER DAMPER 4 18 20 21 22 23 24 DET3 19 S2 S6 G0 G 0 10 V 25 27 28 29 30 31 DET4 N N A A B B 26 S2 S6 G0 G 46 47 48 0 10 V Connections in RCHD Connections in RCHD Connecti...

Страница 5: ...ting of the terminals the panel enters Night mode whereby all dampers close without the controller generating alarms Used for example during intermittent operation Night mode can also be a good safety...

Страница 6: ...arted Use the troubleshooting guide on the display to correct the fault before commissioning Check that the number of fire dampers and smoke detector circuits found match the installation Use the trou...

Страница 7: ...box On Off Damper in middle position Open damper DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLA...

Страница 8: ...r a 5 minute delay which then allows the electric heating coils to cool down Default setting no delay Automatic reset of External incoming alarm Normally an External incoming alarm 34 35 needs to be a...

Страница 9: ...to be replaced This can also be done in connection with service or an obligatory ventilation control OVK Instructions for replacing the battery 1 Power down the unit no 230 V AC must be connected whe...

Страница 10: ...10 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 11: ...11 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 12: ...191203 0001_ENG January 2021 teamfront se www bevent rasch com...

Отзывы: