FENIX2 Monitoring system – Commissioning instruction

3. Commissioning

1.  Power the unit with 230 V AC

2.   Press START on the display and follow the commissioning instructions below.

If a fire damper is connected incorrectly or does not 
work, a red icon will appear.

For safety reasons, a faulty system cannot be 
started. Use the troubleshooting guide on the display 
to correct the fault before commissioning.

Check that the number of fire dampers and smoke 
detector circuits found match the installation.

Use the troubleshooting guide on the display if 
your dampers or smoke detector circuits are not 
displayed.

NB: The icons also show whether the dampers are of 
ON/OFF type or regulating 0-10 V.

The start page when powered up.

Example system with 1 smoke detector circuit and 2 fire dampers with a faulty 
or broken damper.

Example system with 1 smoke detector circuit and 2 fire dampers.

Содержание Fenix 2

Страница 1: ...21 01 2021 FENIX2 Monitoring system Commissioning instruction FIRE SAFETY www bevent rasch com...

Страница 2: ...contains electronic components that can be damaged if used incorrectly When connecting dampers smoke detectors and other con nections the unit must be powered down The cover to access the terminal bl...

Страница 3: ...Modbus TCP or BACnet IP If local control is desired with 0 10 V the FENIX 0 10 V module is used to separate the local control signal from e g a room sensor and the 10 V signal from FENIX2 that takes o...

Страница 4: ...ector RCRD DAMPER DAMPER 3 DAMPER DAMPER 4 18 20 21 22 23 24 DET3 19 S2 S6 G0 G 0 10 V 25 27 28 29 30 31 DET4 N N A A B B 26 S2 S6 G0 G 46 47 48 0 10 V Connections in RCHD Connections in RCHD Connecti...

Страница 5: ...ting of the terminals the panel enters Night mode whereby all dampers close without the controller generating alarms Used for example during intermittent operation Night mode can also be a good safety...

Страница 6: ...arted Use the troubleshooting guide on the display to correct the fault before commissioning Check that the number of fire dampers and smoke detector circuits found match the installation Use the trou...

Страница 7: ...box On Off Damper in middle position Open damper DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLA...

Страница 8: ...r a 5 minute delay which then allows the electric heating coils to cool down Default setting no delay Automatic reset of External incoming alarm Normally an External incoming alarm 34 35 needs to be a...

Страница 9: ...to be replaced This can also be done in connection with service or an obligatory ventilation control OVK Instructions for replacing the battery 1 Power down the unit no 230 V AC must be connected whe...

Страница 10: ...10 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 11: ...11 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 12: ...191203 0001_ENG January 2021 teamfront se www bevent rasch com...