FENIX2 Monitoring system – Commissioning instruction

Function description

Functions and settings via the display

Date and Time 

The date and time are set from the factory, but can be eas-
ily changed on-site if necessary. The unit is equipped with 
automatic summer and winter time adjustment.

Language 

Easily choose between Swedish and English.

Time of functional testing 

Easily set the interval when functional testing of the fire 
dampers is performed and when during the day to do it. 
Selectable ranges: 
• 1 time every 24 hours 
•  1 time every 48 hours  
   (recommended and default setting on delivery)  
• 1 time per week 
• 1 time per month 
• 1 time every 6 months

Perform functional testing 

If necessary, you can easily perform a functional test via 
the display on FENIX2. Can also be performed by shorting 
terminals 32 and 33. 

Device information and communication settings 

Simply set the desired communication settings for Modbus 
TCP or BACnet IP via the display.
IP address is assigned automatically via Dynamic Host Con-
figuration Protocol (DHCP). If a fixed IP address is desired, 
this can be configured via the settings in the touch display. 

Delay External stop 

If desired, functional testing of fire dampers can be delayed 
by 5 minutes. Relay “EXT. STOP” between terminals 44 
and 45 then breaks directly for internal functional testing, 
the functional test of the dampers is performed first after a 
5 minute delay, which then allows the electric heating coils 
to cool down. 
Default setting: no delay.

Automatic reset of External incoming alarm 

Normally an External incoming alarm (34 + 35) needs to be 
acknowledged on the unit via the display or terminal block 
32 + 33 (default setting), this function permits External 
incoming alarms to be acknowledged automatically when 
a possible external alarm stops. Default setting: no auto-
matic reset.

System reset  

The system is easily reset to the default settings when 
necessary. 

Automatic functions integrated in FENIX2

Dynamic troubleshooting diagrams 

Instead of the traditional troubleshooting documents that 
previously accompanied older controllers, FENIX2 shows 
exactly what fault occurred and proposed actions directly 
on the display, such as if a damper does not make contact 
with the limit switch for the closed position: 

The unit then shows exactly what damper fault has been 
identified, which connection terminals and cables should 
be checked and troubleshot. This function facilitates any 
service and troubleshooting in the event of a fault during 
the lifespan of the property. The same pedagogical ap-
proach applies to smoke detector circuits, external alarms 
and other functions that trigger something in the controller.  

Dynamic trouble shooting diagrams and associated action 
texts play an important role in the simplicity of FENIX2. 

Automatic functional testing 

All connected fire dampers are automatically functionally 
tested. In order to ensure that regulating dampers work 
at all damper angles, check the limit switches for both the 
open and closed positions for all connected dampers. 

Содержание Fenix 2

Страница 1: ...21 01 2021 FENIX2 Monitoring system Commissioning instruction FIRE SAFETY www bevent rasch com...

Страница 2: ...contains electronic components that can be damaged if used incorrectly When connecting dampers smoke detectors and other con nections the unit must be powered down The cover to access the terminal bl...

Страница 3: ...Modbus TCP or BACnet IP If local control is desired with 0 10 V the FENIX 0 10 V module is used to separate the local control signal from e g a room sensor and the 10 V signal from FENIX2 that takes o...

Страница 4: ...ector RCRD DAMPER DAMPER 3 DAMPER DAMPER 4 18 20 21 22 23 24 DET3 19 S2 S6 G0 G 0 10 V 25 27 28 29 30 31 DET4 N N A A B B 26 S2 S6 G0 G 46 47 48 0 10 V Connections in RCHD Connections in RCHD Connecti...

Страница 5: ...ting of the terminals the panel enters Night mode whereby all dampers close without the controller generating alarms Used for example during intermittent operation Night mode can also be a good safety...

Страница 6: ...arted Use the troubleshooting guide on the display to correct the fault before commissioning Check that the number of fire dampers and smoke detector circuits found match the installation Use the trou...

Страница 7: ...box On Off Damper in middle position Open damper DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLA...

Страница 8: ...r a 5 minute delay which then allows the electric heating coils to cool down Default setting no delay Automatic reset of External incoming alarm Normally an External incoming alarm 34 35 needs to be a...

Страница 9: ...to be replaced This can also be done in connection with service or an obligatory ventilation control OVK Instructions for replacing the battery 1 Power down the unit no 230 V AC must be connected whe...

Страница 10: ...10 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 11: ...11 BOR S Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX2 Monitoring system Commissioning instruction...

Страница 12: ...191203 0001_ENG January 2021 teamfront se www bevent rasch com...

Отзывы: