FENIX2 Monitoring system – Commissioning instruction
Contents
General ........................................................................................................... 2
Products ......................................................................................................... 3
1. Installation .................................................................................................. 3
2. Connection ................................................................................................. 4
3. Commissioning ........................................................................................... 6
Functions ........................................................................................................ 9
Management and service .............................................................................. 10
General
Control unit FENIX2 contains electronic components that can be damaged if
used incorrectly. When connecting dampers, smoke detectors and other con-
nections, the unit must be powered down!
The cover to access the terminal blocks is removed by unscrewing the cover
on the lower part of the control unit. The connection terminals for 230 V AC are
opened by inserting a screwdriver with a suitable width into the notch above the
connector and then bend the screwdriver slightly upwards.