Maximum Current 1
CFN 04
LCD Display
Range
100 – 800 % of FLA
(Default: 600%)
Description
The Maximum Current 1 parameter is set as a percentage of the Motor FLA (QST 01) parameter setting and
performs two functions. It sets the current level for the end of the ramp profile. It also sets the maximum
current that is allowed to reach the motor after the ramp is completed.
If the ramp time expires before the motor has reached full speed, the starter holds the current at the maximum
current level until either the UTS timer expires, the motor reaches full speed, or the overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower
maximum current.
See Also
Up To Speed Time (QST 09) on page 62.
Start Mode (CFN 01) on page 63.
Ramp Time 1 (QST 08 / CFN 02) on page 64.
Initial Current 1 (QST 06 / CFN 03) on page 64.
Kick Level 1 (CFN 11) on page 68.
Kick Time 1 (CFN 12) on page 69.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramps and Times on page 123.
Ramp Time 2
CFN 05
LCD Display
Range
0 – 300 seconds
(Default: 15 seconds)
Description
The Ramp Time 2 parameter sets the time it takes for the starter to allow the current to go from the initial
current to the maximum current when the second ramp is active. Refer to the Ramp Time 1 (QST 08 / CFN
02) for description of operation.
See Also
Ramp Time 1 (QST 08 / CFN 02) on page 64.
Digital Input Configuration (I/O 01-08) on page 90.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramp and Times on page 123.
Theory of Operation section 7.3.6, Dual Acceleration Ramp Control on page 128.
Initial Current 2
CFN 06
LCD Display
Range
50 – 600 % of FLA
(Default: 100%)
Description
The Initial Current 2 parameter is set as a percentage of the Motor FLA (QST 01) parameter setting when the
second ramp is active. Refer to the Initial Current 1 (CFN 03) parameter for description of operation.
See Also
Initial Current 1 (CFN 03) on page 64.
Digital Input Configuration (I/O 01-08) on page 90.
Theory of Operation section 7.3.1, Current Ramp Settings, Ramps and Times on page 123.
Theory of Operation section 7.3.6, Dual Acceleration Ramp Control on page 128.
65
6 - PARAMETER DESCRIPTION
CFN: Ramp Time 2
05
15 sec
CFN: Init Cur 2
06
100 %
CFN: Max Cur 1
04
600 %
Содержание RediStart EXEXMVRMX3 Series
Страница 2: ......
Страница 10: ......
Страница 11: ...1 Introduction 1...
Страница 17: ...2 Technical Specifications 7...
Страница 27: ...3 Installation 17...
Страница 38: ...EXMVRMX3 I O Card Layout 3 9 EXMVRMX3 I O Card Layout 28 3 INSTALLATION Figure 11 EXMVRMX3 I O Card Layout...
Страница 48: ......
Страница 49: ...4 Keypad Operation 39...
Страница 59: ...5 Parameter Groups 49...
Страница 67: ...6 Parameter Description 57...
Страница 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Страница 123: ...7 Theory of Operation 113...
Страница 155: ...NOTES 145 7 THEORY OF OPERATION...
Страница 156: ...146 7 THEORY OF OPERATION...
Страница 157: ...8 Troubleshooting Maintenance 147...
Страница 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Страница 186: ......
Страница 187: ...Appendices 177...
Страница 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Страница 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...