L2-L3 Volts
Voltage in, L2 to L3 RMS.
L3-L1 Volts
Voltage in, L3 to L1 RMS.
Overload
Thermal overload in %.
Power Factor
Motor power factor.
Watts
Motor real power consumed.
VA
Motor apparent power consumed.
vars
Motor reactive power consumed.
kW hours
Kilo-watt-hour used by the motor, wraps at 1,000.
MW hours
Mega-watt-hour used by the motor, wraps at 10,000.
Phase Order
Phase Rotation.
Line Freq
Line Frequency.
Analog In
Analog Input %.
Analog Out
Analog Output %.
Run Days
Running time in days, wraps at 2,730 days.
Run Hours
Running time in Hours and Minutes, wraps at 24:00.
Starts
Number of Starts, wraps at 65,536.
TruTorque %
TruTorque %.
Power %
Power %.
Pk accel Curr
Peak starting current.
Last Start T
Last starting duration.
Zero Seq GF
Zero sequence ground fault.
Stator Temp
Highest Stator temperature.
Bearing Temp
Highest Bearing temperature.
Other Temp
Highest Other temperature.
All Temp
Highest of all temperatures.
Description
Parameters FUN 01 and FUN 02 configure which meters are displayed on the two lines of the main display
screen.
CT Ratio
FUN 03
LCD Display
Range
72:1, 96:1, 144:1, 288:1, 864:1, 2640:1, 3900:1, 5760:1, 8000:1, 14400:1, 28800:1, 50:5, 150:5, 250:5, 800:5,
2000:5, 5000:5
(Default: 288:1)
Description
The CT Ratio parameter must be set to match the CTs (current transformers) supplied with the starter. This
allows the starter to properly calculate the current supplied to the motor.
z
NOTE:
It is very important that the CT ratio is set correctly. Otherwise, many starter functions will not
operate correctly.
Input Phase Sensitivity
FUN 04
LCD Display
Range
LCD
Description
Insensitive
Runs with any three phase sequence.
(Default)
ABC
Only runs with ABC phase sequence.
CBA
Only runs with CBA phase sequence.
Single phase
Single Phase.
Description
The Phase Order parameter sets the phase sensitivity of the starter. This can be used to protect the motor from
a possible change in the incoming phase sequence. If the incoming phase sequence does not match the set
phase rotation, the starter displays an alarm while stopped and faults if a start is attempted.
102
6 - PARAMETER DESCRIPTION
FUN:
CT Ratio
03
50:5
FUN: Phase Order
04
Insensitive
Содержание RediStart EXEXMVRMX3 Series
Страница 2: ......
Страница 10: ......
Страница 11: ...1 Introduction 1...
Страница 17: ...2 Technical Specifications 7...
Страница 27: ...3 Installation 17...
Страница 38: ...EXMVRMX3 I O Card Layout 3 9 EXMVRMX3 I O Card Layout 28 3 INSTALLATION Figure 11 EXMVRMX3 I O Card Layout...
Страница 48: ......
Страница 49: ...4 Keypad Operation 39...
Страница 59: ...5 Parameter Groups 49...
Страница 67: ...6 Parameter Description 57...
Страница 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Страница 123: ...7 Theory of Operation 113...
Страница 155: ...NOTES 145 7 THEORY OF OPERATION...
Страница 156: ...146 7 THEORY OF OPERATION...
Страница 157: ...8 Troubleshooting Maintenance 147...
Страница 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Страница 186: ......
Страница 187: ...Appendices 177...
Страница 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Страница 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...