Power Wiring
3.6
Power Wiring
Input Line Requirements
The input line source needs to be an adequate source to start the motor, generally 2 times the rating of the motor FLA. (This may not
apply in some cases such as being connected to a generator).
3.6.1
Recommended Wire Gauges
The wire gauge selection is based on the FLA of the motor. Refer to NEC table 310-16 or CEC Part 1, Table 2 or local code
requirements for selecting the correct wire sizing. Ensure appropriate wire derating for temperature is applied. If more than three current
carrying conductors are in one conduit, ensure NEC table 310.15(B)(2) or CEC Part 1 Table 5C is adhered to. In some areas local codes
may take precedence over the NEC. Refer to your local requirements.
3.6.2
Power Wire Connections
Attach the motor cables:
•
Use the T1, T2 and T3 terminals. Use lugs/crimps or terminals (lugs and crimps are to be provided by the user).
Attach the power source cables:
•
Use the L1, L2 and L3 terminals. Use lugs/crimps or terminals (lugs and crimps are to be provided by the user).
3.6.3
Motor Lead Length
The standard starter can operate a motor with a maximum of 600 feet of properly sized cable between the “T” leads of the starter and that
of the motor. For wire runs greater than 600 feet contact Benshaw Inc. for application assistance. If shielded cable is used, consult
factory for recommended length.
3.6.4
Compression Lugs
The following is a list of the recommended crimp-on wire connectors manufactured by Penn-Union Corp. for copper wire.
23
3 - INSTALLATION
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0S20
500 MCM
BLU-050S2
2/0
BLU-2/0S4
600 MCM
BLU-060S1
3/0
BLU-3/0S1
650 MCM
BLU-065S5
4/0
BLU-4/0S1
750 MCM
BLU-075S
250 MCM
BLU-025S
800 MCM
BLU-080S
300 MCM
BLU-030S
1000 MCM
BLU-100S
350 MCM
BLU-035S
1500 MCM
BLU-150S
400 MCM
BLU-040S4
2000 MCM
BLU-200s
450 MCM
BLU-045S1
Table 8: Single Hole Compression Lugs
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0D20
500 MCM
BLU-050D2
2/0
BLU-2/0D4
600 MCM
BLU-060D1
3/0
BLU-3/0D1
650 MCM
BLU-065D5
4/0
BLU-4/0D1
750 MCM
BLU-075D
250 MCM
BLU-025D
800 MCM
BLU-080D
300 MCM
BLU-030D
1000 MCM
BLU-100D
350 MCM
BLU-035D
1500 MCM
BLU-150D
400 MCM
BLU-040D4
2000 MCM
BLU-200D
450 MCM
BLU-045D1
Table 9: Two Hole Compression Lugs
Содержание RediStart EXEXMVRMX3 Series
Страница 2: ......
Страница 10: ......
Страница 11: ...1 Introduction 1...
Страница 17: ...2 Technical Specifications 7...
Страница 27: ...3 Installation 17...
Страница 38: ...EXMVRMX3 I O Card Layout 3 9 EXMVRMX3 I O Card Layout 28 3 INSTALLATION Figure 11 EXMVRMX3 I O Card Layout...
Страница 48: ......
Страница 49: ...4 Keypad Operation 39...
Страница 59: ...5 Parameter Groups 49...
Страница 67: ...6 Parameter Description 57...
Страница 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Страница 123: ...7 Theory of Operation 113...
Страница 155: ...NOTES 145 7 THEORY OF OPERATION...
Страница 156: ...146 7 THEORY OF OPERATION...
Страница 157: ...8 Troubleshooting Maintenance 147...
Страница 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Страница 186: ......
Страница 187: ...Appendices 177...
Страница 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Страница 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...