Rated RMS Voltage
FUN 05
LCD Display
Range
100, 110, 120, 200, 208, 220, 230, 240, 350, 380, 400, 415, 440, 460, 480, 500, 525, 575, 600, 660, 690, 800,
1000, 1140, 2200, 2300, 2400, 3300, 4160, 4600, 4800, 6000, 6600, 6900, 10.00K, 11.00K, 11.50K, 12.00K,
12.47K, 13.20K, 13.80K
(Default: 480)
Description
The Rated Voltage parameter sets the line voltage that is used when the starter performs Over and Under line
voltage calculations. This value is the supply voltage, NOT the motor utilization voltage.
z
NOTE:
Settings above 1140V are for medium voltage applications.
z
NOTE:
Rated Voltage must be set properly for the starter to operate properly.
See Also
Over Voltage Level parameter (PFN 10) on page 81.
Under Voltage Level parameter (PFN 11) on page 81.
Voltage Trip Time parameter (PFN 12) on page 81.
Meter parameter (FUN 01, FUN 02) on page 101.
Motor Rated Power Factor
FUN 06
LCD Display
Range
-0.01 lag to 1.00 unity
(Default: –0.92)
Description
The Motor Rated Power Factor parameter sets the motor power factor value that is used by the MX
3
starter for
TruTorque and Power control calculations and metering calculations.
If TruTorque or Power acceleration and/or deceleration control is used, it is very important to properly set this
parameter to the motor's full load rated power factor (usually available on the motor nameplate or from the
motor manufacturer). For a typical induction motor, this value is between 0.80 and 0.95.
If the motor rated power factor is not available from either the motor nameplate or the motor manufacturer, the
value can be obtained by viewing the power factor meter.
With the motor running at full name plate current, view the power factor meter by pressing the [UP] arrow key
until the Motor PF meter is displayed using the LCD display.
The meter value can be entered into the Rated Power Factor parameter.
See Also
Meter parameters (FUN 01, FUN 02) on page 101.
Theory of Operation section 7.3.3, TruTorque Acceleration Control Settings and Times on page 124.
Theory of Operation section 7.3.4, Power Control Acceleration Settings and Times on page 126.
Starter Type
FUN 07
LCD Display
Range
LCD
Description
Normal
Normal Reduced Voltage Soft Starter RVSS.
(Default)
Inside Delta
Inside Delta, RVSS. - Consult Factory
Wye-Delta
Wye Delta.
Phase Ctl
Open Loop Phase control using external analog input reference. - Consult Factory
103
6 - PARAMETER DESCRIPTION
FUN: Rated Volts
05
2200
Vlt
FUN: Motor PF
06
–0.92
FUN: Starter Type
07
Normal
Содержание RediStart EXEXMVRMX3 Series
Страница 2: ......
Страница 10: ......
Страница 11: ...1 Introduction 1...
Страница 17: ...2 Technical Specifications 7...
Страница 27: ...3 Installation 17...
Страница 38: ...EXMVRMX3 I O Card Layout 3 9 EXMVRMX3 I O Card Layout 28 3 INSTALLATION Figure 11 EXMVRMX3 I O Card Layout...
Страница 48: ......
Страница 49: ...4 Keypad Operation 39...
Страница 59: ...5 Parameter Groups 49...
Страница 67: ...6 Parameter Description 57...
Страница 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Страница 123: ...7 Theory of Operation 113...
Страница 155: ...NOTES 145 7 THEORY OF OPERATION...
Страница 156: ...146 7 THEORY OF OPERATION...
Страница 157: ...8 Troubleshooting Maintenance 147...
Страница 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Страница 186: ......
Страница 187: ...Appendices 177...
Страница 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Страница 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...