8 - TROUBLESHOOTING & MAINTENANCE
8.4.7
Metering incorrect
Condition
Cause
Solution
Power Metering not reading correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.
CT1=L1 CT2=L2 CT3=L3
CT ratio parameter (FUN03) set
incorrectly.
Verify that the CT ratio parameter is set
correctly.
PF Meter not reading correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.
Motor Current or Voltage meters
fluctuating with steady load.
Energy Saver active.
Turn off Energy Saver if not desired.
Loose connections.
Shut off all power and check all
connections.
SCR fault.
Verify that the SCRs gate leads are
connected properly and the SCRs are
ok.
Load actually is not steady.
Verify that the load is actually steady
and that there are not mechanical issues.
Other equipment on same power feed
causing power fluctuations and/or
distortion.
Fix cause of power fluctuations and/or
distortion.
Voltage Metering not reading correctly.
In medium voltage systems, Rated
Voltage parameter (FUN05) set
incorrectly.
Verify that Rated Voltage parameter is
set correctly.
Current Metering not reading correctly.
CT ratio parameter (FUN03) set
incorrectly.
Verify that the CT ratio (FUN03)
parameter is set correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.CT1=L1
CT2=L2 CT3=L3
Residual Ground Fault Current Metering
not reading correctly.
CT ratio parameter (FUN03) set
incorrectly.
Verify that the CT ratio parameter is set
correctly.
CTs installed or wired incorrectly.
Verify correct CT wiring and verify that
the CTs are installed with all the White
dots towards the input line side.CT1=L1
CT2=L2 CT3=L3
Zero Sequence GF Metering not reading
correctly.
CT installed or wired incorrectly.
Verify CT installation.
Содержание RediStart EXEXMVRMX3 Series
Страница 2: ......
Страница 10: ......
Страница 11: ...1 Introduction 1...
Страница 17: ...2 Technical Specifications 7...
Страница 27: ...3 Installation 17...
Страница 38: ...EXMVRMX3 I O Card Layout 3 9 EXMVRMX3 I O Card Layout 28 3 INSTALLATION Figure 11 EXMVRMX3 I O Card Layout...
Страница 48: ......
Страница 49: ...4 Keypad Operation 39...
Страница 59: ...5 Parameter Groups 49...
Страница 67: ...6 Parameter Description 57...
Страница 122: ...NOTES 112 6 PARAMETER DESCRIPTION...
Страница 123: ...7 Theory of Operation 113...
Страница 155: ...NOTES 145 7 THEORY OF OPERATION...
Страница 156: ...146 7 THEORY OF OPERATION...
Страница 157: ...8 Troubleshooting Maintenance 147...
Страница 185: ...NOTES 175 8 TROUBLESHOOTING MAINTENANCE...
Страница 186: ......
Страница 187: ...Appendices 177...
Страница 213: ...203 APPENDIX H 3 YEAR WARRANTY...
Страница 221: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...